BALANCING PROCEDURE
The
START
button will start the balancing process. The START button will only be
enabled if there are two or more registers in the register list.
The first step of the balancing procedure is to take an initial sweep of all registers
within the selected branch with all dampers open.
Red indicates that a reading still needs to be taken from the register. After selecting
the register to measure, its button will turn from red to white, indicating that it is the
active register.
Press the register button again to store the reading, at which point it will change from
white to green, indicating that a value has been stored for that register.
Repeat this procedure until all of the registers have been measured. Pressing on a
register again allows for a retaking of that register if needed.
If the slide out menu is opened, the following choices will be shown.
“Screen Timed Out Settings” allows the hibernate mode to be turned on. If the option
is turned on, then the current screen will hibernate after timing out based on the
handheld instrument’s hibernate time in the Settings->Display->Sleep setting. If the
option is turned off, then the device will stay awake and not go into hibernation. This is
also available on the Initial Reading, Balancing, and Final Reading screens.