RMO200
Error Messages
10.3 Error Message " Polarity VS"
This message is displayed if the polarity of measuring cables is incorrect.
In this case connect measuring cables correct and repeat the test.
10.4 Error Message "Change Current"
This message is displayed if the selected test current is too high.
In this case reduce the test current and repeat the test.
10.5 Error Message "Overheat"
This message is displayed when RMO200’s operating temperature rises too
high due to a high ambient temperature or, despite the duty cycle time control,
too many high current tests were performed in too short of a time.
In this case, wait for the test set to cool down and repeat the test.
10.6 Error Message "Malfunction"
If this message is shown on the display, or if RMO200 cannot be operated
anymore at all, a serious internal error occurred.
Please do not open RMO200 by yourself. Contact the IBEKO POWER AB
(refer to section ”Manufacturer Contact Information”).
10.6Error Message "Mains Voltage < 90V"
This message is displayed when RMO200’s mains voltage is below 90 V.
In this chase to remove the status message you must restart RMO200.