9
8
DLC-010 as stand-alone unit
Connect a 230VAC power source to the circuit breaker on the DIN-rail.
Connect the ground wire to the grounding terminal block (next to the
circuit breaker)
Connect the motor power wires to the “Cover motor (24VDC)”
connection terminal and the motor sensor wires to the “Cover motor
sensor” connection terminal blocks in the DLC-010. (terminal nrs 1, 2, 3,
4, 5)
Connect the ‘open’ and ‘close’ terminals of the key switch to the key
switch terminal blocks (terminal nrs 9, 10, 11, 12)
Make sure DIP switch 1 is set to the OFF position, so the DLC-010 will be
controlled locally, via the keyswitch
After installation:
Switch on the main power. The status LED should be blue (“not calibrated”
mode - see page 12 for details).
Turn the key switch and check if the motor is rotating the correct way
(keyswitch turned to open - cover needs to open). If this is not the case,
then swap the motor power cables (see picture next page: switch the red
and grey wires - terminal nrs 1 & 2)
Installation instructions
1.
2.
3.
4.
5.
ON
1 2 3
DIP switch 1 to OFF:
Local control (via Keyswitch)
is activated
230VAC
Nr. Description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Cover motor (24VDC)
Cover motor (24VDC)
Cover motor sensor: Power
Cover motor sensor: Ground
Cover motor sensor: Data
Cover motor sensor: Optional
CAN_L
CAN_H
Nr. Description
Turnkey
Turnkey
Turnkey
Turnkey
Relay NC (for filtration pump)
Relay NC (for filtration pump)
TERMINAL BLOCK DESIGNATION
}
Cover OPEN
}
Cover CLOSE
Optional:
Terminal nrs 13 and 14 can be used to connect a fi ltration pump.
The DLC-010 will activate or disable the fi ltration pump, depending on the
position of the cover and/or the operation mode. See page 14 for details.