Dunkirk GWB9-050IH-2 Installation Instructions Manual Download Page 45

45

Maintenance As Outlined Below Can Be 

Performed By Owner Unless Otherwise Noted.

• The acidic nature of 

fl

 ue gasses condensing on 

aluminum boiler sections may cause formation of 

aluminum oxide. This oxide formation is normal, 

is generally uniform throughout boiler sections, 

and represents negligible mass of aluminum that is 

consumed by oxidation during life of the boiler. 

• If left unchecked, this buildup may eventually cause 

blockage of 

fl

 ue gas passages in boiler sections, 

reducing ef

fi

 ciency, and ultimately shutting down the 

boiler due to lack of combustion air 

fl

 ow. 

• Regular service and maintenance by a quali

fi

 ed service 

agency must be performed to assure safe trouble free 

operation and maximum ef

fi

 ciency.

Beginning Of Each Heating Season

1. 

Annual service call by quali

fi

 ed service agency, which 

includes:
A. Examine 

fl

 ue passages between boiler sections, 

burner, and condensate lines, and clean if 

necessary following 

 

“Annual Examination And 

Cleaning Of Boiler Components” on page 46

 .

B.  Visually inspect venting and air intake system 

for proper function, deterioration or leakage. If 

vent or air intake show any signs of deterioration 

or leakage, repair or replace them, immediately. 

Insure proper reassembly and resealing of vent and 

air intake system

C.  Check for and remove any obstruction to 

fl

 ow of 

combustion air or venting of 

fl

 ue gases. Check air 

baf

fl

 e located inside 1½” x 2” 

fl

 exible coupling on 

mixer, clean if necessary and make sure to put it 

back. Refer to repair parts diagram of mixer and 

pressure switch assembly for exact location.

D.  Follow instructions for

 

“Operating Instructions” on 

page 38

 .

E.  Follow instructions for “Check Out Procedure and 

Adjustment” on page 42 .

F.  Visually inspect condensate drain lines for proper 

operation and deterioration. Check for plugged 

condensate drain lines.

G.  Check silicone rubber seals between boiler sections. 

Insure that there are no leaks. Use RTV silicone 

rubber adhesive sealant rated for at least 400° F to 

replace or repair seals in locations where original 

seals have deteriorated.

H.  Check all gasketed joints for leakage, and tighten 

bolts or replace gaskets if necessary.

I.  Remove jacket front and top panels and check for 

piping leaks around relief valve and other 

fi

 ttings. 

Repair, if found. DO NOT use stop leak compounds.

2. 

Check boiler area is free from combustible materials, 

gasoline, and other 

fl

 ammable vapors and liquids.

3. 

Circulator pump and blower motor furnished with boiler 

are permanently lubricated from factory and require no 

further lubrication. Additional or non-factory supplied 

pumps and/or motors should be lubricated according to 

the pump and/or motor manufacturer’s instruction. 

Daily During Heating Season

1. 

Check for and remove any obstruction to the 

fl

 ow of 

combustion air or venting of 

fl

 ue gases.

2. 

Check boiler area is free from combustible materials, 

gasoline, and other 

fl

 ammable vapors and liquids.

 MAINTENANCE AND CLEANING

Monthly During Heating Season

1. 

Remove jacket front and top panels and check for 

piping leaks around relief valve and other 

fi

 ttings. If 

found, contact quali

fi

 ed service agency to repair. DO 

NOT use stop leak compounds.

2. 

Test relief valve. Refer to valve manufacturers 

instructions packaged with relief valve.

3. 

Visually inspect venting and air intake system for 

proper function, deterioration, or leakage. If vent or 

air intake show any signs of deterioration or leakage, 

contact a quali

fi

 ed service agency to repair or replace 

immediately and to insure proper reassembly and 

resealing of vent and air intake system.

4. 

Visually inspect clear vinyl condensate lines and PVC 

condensate drain pipe for proper operation, leakage, 

and deterioration. If condensate lines or drain pipe 

show any signs of blockage, leakage, or deterioration 

contact a quali

fi

 ed service agency to clean, repair, or 

replace them immediately.

Periodically During Heating Season

Where low water cutoffs are used, periodic inspection of 

low water cut off is necessary, including 

fl

 ushing of 

fl

 oat 

type devices. Refer to low water cut off manufacturer’s 

speci

fi

 c instructions.

End of Each Heating Season - Annual Shutdown 

Procedure

Follow instructions  “To Turn Off Gas To Appliance” on page 

38 .
If heating system is to remain out of service during 

freezing weather, and does not contain antifreeze, drain 

system completely. If boiler will be exposed to freezing 

temperatures, drain condensate lines. Otherwise, do not 

drain system or boiler.

Summary of Contents for GWB9-050IH-2

Page 1: ...fired hot water boilers are design certified by CSA Canadian Standards Association for use with natural and propane gases 100 MBH model is certified for natural gas only They are constructed and hydro...

Page 2: ...2 DIMENSIONS 2 2 Figure 1 Boiler Dimensions...

Page 3: ...Piping 11 Combustion Air And Vent Pipe 22 Gas Supply Piping 28 Electrical Wiring 30 Controls And Accessories 35 Start Up 37 Operating Instructions 38 S9381a Integrated Boiler Control Operation And Adj...

Page 4: ...address practices not related to personal injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury WARNING Indicates a hazardous situation which if...

Page 5: ...minal units i e finned tube baseboard cast iron radiators radiant floor etc The difference between Heating Capacity and Net AHRI Rating called piping and pickup allowance establishes reserve for heati...

Page 6: ...LLATIONS Boilers with exception of 90 75 propane LP product are factory equipped for operation at altitudes ranging from 0 10 000 feet above sea level No changes to factory settings are required for i...

Page 7: ...0 5 000 5 000 10 000 Normal Input MBH 75 Manifold Pressure In W C 2 5 3 5 3 5 3 5 3 3 Orifice 43331093 43331096 For model 90 75 Propane units only at altitudes above 5 000 ft install 90 75 High Altitu...

Page 8: ...may be used to raise boiler 1 Boiler is equipped for residential installations If used for commercial applications any additional code requirements must be adhered to for installation This may require...

Page 9: ...through piping systems without restrictions for boiler operation 7 Install boiler such that the automatic gas ignition system components are protected from water dripping spraying rain etc during ope...

Page 10: ...the venting system for proper size and horizontal pitch and determine there is no blockage or restrictions leakage corrosion and other deficiencies which could cause an unsafe condition BOILER INSTALL...

Page 11: ...of radiation units panels radiators baseboard or tubing and supply and return mains After all heating system piping and components have been installed make final connection of system piping to boiler...

Page 12: ...12 NEAR BOILER PIPING Figure 2 Single Zone Boiler Piping...

Page 13: ...ly to have small zones with very low heat and flow requirements compared to full heating capacity of the boiler This can result in very low flow in the boiler if only one small zone is calling for hea...

Page 14: ...14 Figure 4 Two Zone Boiler Piping With Circulators NEAR BOILER PIPING...

Page 15: ...15 NEAR BOILER PIPING Figure 5 Primary Secondary Piping And Wiring With Circulators And Domestic Hot Water...

Page 16: ...16 NEAR BOILER PIPING Figure 6 Piping and Wiring Primary Secondary Multi Zone System Piping With Zone Valves And Domestic Hot Water With Zone Valve...

Page 17: ...17 NEAR BOILER PIPING Figure 7 Piping And Wiring Primary Secondary Piping With Zone Valves And Domestic Hot Water With Circulator...

Page 18: ...nate pipe with plain end not threaded Expansion Tank And Make Up Water Determine required system fill pressure system design temperature and system water content Boiler contains 2 6 gallons U S Size e...

Page 19: ...19 Figure 9 Diaphragm Type Expansion Tank Piping NEAR BOILER PIPING...

Page 20: ...20 Figure 10 Conventional Closed Type Expansion Tank Piping NEAR BOILER PIPING...

Page 21: ...required to initially fill condensate trap for start up Steps are only required at initial start up or if maintenance requires draining of condensate trap 1 Disconnect vent condensate drain line from...

Page 22: ...condensate Due to potential for flue gas temperatures over 155 F first five 5 feet of vent pipe must be CPVC the remain ing vent pipe can be PVC If any elbows are employed within the first 5 feet of...

Page 23: ...ZE 2 PIPE MINIMUM VENTING 2 PIPE MAXIMUM VENTING 3 PIPE MINIMUM VENTING 3 PIPE MAXIMUM VENTING 100 2 FEET 21 FEET 15 FEET 92 FEET 75 50 2 FEET 26 FEET 20 FEET 112 FEET Vent shall not terminate underne...

Page 24: ...24 Figure 12 Roof Vent Intake Terminations COMBUSTION AIR AND VENT PIPE VENT AIR INTAKE...

Page 25: ...Wall Vent Intake terminations Less Than 12 Clearance Above Grade Figure 14 Side Wall Vent Intake Terminations 12 Or More Clearance Above Grade COMBUSTION AIR AND VENT PIPE Less Than 12 Clearance 12 O...

Page 26: ...imum Overhang VENT COMBUSTION AIR COMBUSTION AIR 1 MAXIMUM NOTE SECURING STRAP MUST BE FIELD INSTALLED TO PREVENT MOVEMENT OF TERMINATION KIT IN SIDE WALL ELBOW FIELD SUPPLIED A A B B C C STRAP FIELD...

Page 27: ...for 90 50 and 90 75 models 2 feet minimum total equivalent length for all models TRANSITION FITTING 2 50 8mm to 3 76 2mm IN VERTICAL RUN 3 76 2mm DIAMETER VENT AND COMBUSTION AIR INTAKE PIPING 92 fee...

Page 28: ...ly pressure See Table 7 Page 29 3 Use ground joint unions 4 Provide sediment trap up stream of gas valve 5 Use two pipe wrenches when making the connection to gas valve to keep it from turning 6 Insta...

Page 29: ...000 40 63 000 130 000 245 000 445 000 60 50 000 105 000 195 000 365 000 PROPANE GAS Length of Pipe Ft Pipe Capacity BTU Per Hour Input Includes Fittings Copper Tubing Iron Pipe 5 8 3 4 1 2 3 4 20 131...

Page 30: ...m Follow instructions included with your thermostat Locate thermostat about five feet above floor on inside wall Mount directly on wall or on vertical mounted outlet box It should be sensing average r...

Page 31: ...31 Figure 20 Wiring Schematic ELECTRICAL WIRING NOTICE If any of original wire as supplied with this appliance must be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent...

Page 32: ...32 Figure 21 Ladder Wiring Diagram ELECTRICAL WIRING...

Page 33: ...33 Figure 22 Suggested Wiring Schematic for Domestic Hot Water Priority Two Zone System with Circulators Using Argo AR822II Pump Relay ELECTRICAL WIRING...

Page 34: ...34 Figure 23 Ladder Diagram for Figure 22 ELECTRICAL WIRING...

Page 35: ...ntroller from thermal purge and allow burner to run in order to maintain comfort in the space Boiler temperature has dropped 10 F from boiler water temperature measured at beginning of the call for he...

Page 36: ...zone or zone valve controlled heating system and should be located on downstream i e pumping away side of expansion tank For pump controlled system where there is a circulator for each zone circulato...

Page 37: ...mediately Purging Air For Systems With Conventional Closed Type Expansion Tanks Refer to the appropriate diagrams Near Boiler Piping on page 11 for more information 1 Close all zone service valves on...

Page 38: ...e front jacket panel OPERATING INSTRUCTIONS WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This applianc...

Page 39: ...Press and release the I button until the parameter requiring adjustment is displayed Then press the UP or DOWN button until the parameter has reached the desired value After 60 seconds without any bu...

Page 40: ...40 S9381A INTEGRATED BOILER CONTROL OPERATION AND ADJUSTMENTS Table 9 State Code Definitions...

Page 41: ...41 S9381A INTEGRATED BOILER CONTROL OPERATION AND ADJUSTMENTS Figure 26 Sequence of Operation...

Page 42: ...controls test for operation as outlined by control manufacturer Burner should be operating and should go off when controls are tested When safety controls are restored burner should reignite Set Therm...

Page 43: ...fold pressure lower than 2 0 inches w c or higher than 3 0 inches w c when adjusting input rate IV Measure new input rate cover screw must be installed Repeat steps I IV until the input rate is within...

Page 44: ...GULATOR ADJUSTMENT UNDER CAP SCREW INLET PRESSURE TAP VR8205 WIRING TERMINALS 2 OUTLET PRESSURE TAP Figure 27 Manifold Pressure Measurement Detail Figure 28 Gas Valve CHECK OUT PROCEDURE AND ADJUSTMEN...

Page 45: ...place gaskets if necessary I Remove jacket front and top panels and check for piping leaks around relief valve and other fittings Repair if found DO NOT use stop leak compounds 2 Check boiler area is...

Page 46: ...ent pipe connector to draft inducer outlet MAINTENANCE AND CLEANING Annual Examination And Cleaning Of Boiler Components DANGER Before servicing turn off electrical power to boiler at service switch C...

Page 47: ...Service Checks 1 Before troubleshooting A Make sure that circuit breaker is on or fuse is ok at electrical panel B Make sure that service switch is on C Make sure that gas is on at the gas meter at a...

Page 48: ...48 TROUBLESHOOTING Table 10 Error Codes...

Page 49: ...BOILER STATUS DIFFERENTIAL PRESSURE W C PRESSURE SWITCH CONNECTS Not Running 0 Normally Open Setpoint 1 00 for Model 100 1 60 for Model 75 2 10 for Model 50 Running Without Blockage Greater Than Setpo...

Page 50: ...njury Install boiler so gas ignition system components are protected from water dripping spraying rain etc during appliance operation and service circulator re placement etc DIELECTRIC ISOLATION Two 2...

Page 51: ...or any other open type system Fill Water and Chemistry Verify water used to fill system meets these requirements System fluid pH maintained between 7 0 and 8 0 Maintain water hardness below 7 grains...

Page 52: ...ed to maintain a pH within recommended level Follow antifreeze manufacturer s instructions to adjust pH If system has leaked water and antifreeze chemistry will need to be adjusted To avoid damage to...

Page 53: ...stributor 15363 117 Avenue Edmonton AB T5M 3X4 Canada www hydronicagencies com Tel 780 452 8661 Fax 780 488 2304 Fernox www fernox com Intercool NFP 30 40 50 AA Intercool RPH 15 Interstate Chemical 27...

Page 54: ...____ Installation instructions have been followed Checkout procedure and adjustments performed Maintenance and Service issues reviewed with owner maintenance person Installation booklet affixed on or...

Page 55: ...55 NOTES...

Page 56: ...PRODUCT LITERATURE Lennox Industries Inc Dallas Texas Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Reviews: