Adjusting the outlet pressure (type HD and ND,MD
for 1", 1 1/2" i DN25)
The regulator is adjusted by turning the adjustment
screw B.
1. Remove the protective cap A.
2. Turn the external adjusting screw B using the Allen key
size.
3. Clockwise rotation: Increases the initial tension of the
adjustment spring, thus increasing (+) the outlet pres
-
sure p
ds
.
4. Counterclockwise rotation: Discharges the adjustment
spring, reducing (-) the outlet pressure p
ds
.
5. After the setting: Screw on the protective cap A again.
B
A
E
F
D