9.2 Installation instructions
•
The installation must be carried out according to the
installation scheme specified below.
•
Installation of the safety shut-off valve in the flow
direction (arrow/housing).
•
Design a straight stabilisation section with the same
diameter.
•
Run pulse line clean and burr-free. Distance > 5 x DN
Pos. Designation
1
Shut-off valve, inlet side (e.g. ball valve or butterfly valve)
2
Filter
3
Welded part
4
Pressure gauge, inlet side
5
Regulator with SAV integrated
6
Stabilisation section
7
Pressure gauge, outlet side
8
Pushbutton cock
9
SBV
10
Venting ball valve
11
Shut-off valve outlet side (e.g. DMV)
12
Breathing connection regulator
13
Breathing connection SAV
14
Relief connection SBV
•
Maximum flow velocity in the stabilisation section:
≤ 30 m/s.
•
(Version of the pulse lines: steel pipe D= 12 x 1.5, only
with external pulse)
•
(Avoid accumulation of condensate: install the pulse
lines with a gradient, only with external pulse.)
1
2
3
4
5
8
6
7
9
11
10
12
Stabilisation section
> 5 x DN
Installation scheme
13
14