background image

13

9.  Electronical Installation

a.  Removing / replacing components

Removing paired components from the network or replacing is only possible within 30 minutes after the 
component is paired in or is restarted. 
Restarting can be done by disconnecting the power for a moment. 
After a time-span of 30 minutes, remove and replace operations are ignored.

Removing a component

1.

Activate ‘Installer mode’ by long-pressing 2 diagonal 
buttons on a paired control
. The LED will flash green 
rapidly. 

2.

Press once and hold a button on the component to be 
removed in order to remove it from the network. 

3.

Deactivate ‘Installer mode’ by pressing the 4 buttons 
on a paired control simultaneously (or using the palm 
of your hand on a control featuring touch buttons). The 
LED will turn white. 

Summary of Contents for DucoBox Energy Premium

Page 1: ...DucoBox Energy Premium HANDS ON BE en...

Page 2: ...sensor only one boxsensor can be connected Pressure sensors Supply Fan Heater 2 Zone Bypass HIGH LOW INST Power 230 VAC Temperature sensors Extract fan DUCO Wired Antenna DUCO Network Tool Switch Cont...

Page 3: ...king slowly In network GREEN blinking rapidly In network waiting for associated components YELLOW blinking slowly Transitional phase please wait YELLOW on Initialising system configuration in progress...

Page 4: ...by means of stickers Fresh air Stale air RIGHT HAND configuration EHA SUP1 SUP2 ETA ODA OUTDOORS HOUSE LEFT HAND configuration EHA SUP1 SUP2 ETA ODA OUTDOORS HOUSE Air ducts to HOUSE Air ducts to OUT...

Page 5: ...steps you can proceed with the following steps in order to complete the installation Pairing control components to the DucoBox Energy Premium 5 a DucoBox Energy Premium air side calibration If there a...

Page 6: ...ou are utilising an integrated 2 zone system Zone 1 is the bevelled side of the DucoBox Energy Premium in each case b Pairing control components with the DucoBox Energy Premium 1 Activate advanced mod...

Page 7: ...entire system I e DucoBox Energy Premium without a 2 zone system 1Z types all components DucoBox Energy with a 2 zone system 2Z types components in wet rooms only bathroom toilet kitchen laundry etc 4...

Page 8: ...g enter 6 For 2 zone system only Pair the desired control components with zone 2 This could be the night zone bedrooms etc Then confirm by pressing enter All components have now been paired This wizar...

Page 9: ...this removes all paired control components from the network FACTORY RESET this resets the entire system DucoBox Energy Premium paired components to factory settings The calibration will be lost Use t...

Page 10: ...pending on the situation in accordance with the table below In order to configure the air supply and exhaust correctly these vents must be set so they match the desired flow rate in line with the tabl...

Page 11: ...r each zone if asked to do so 3 In the Adjust the supply vents step select the duct with the highest flow rate and resistance and using a pressure compensated air flow meter measure the flow rate at t...

Page 12: ...vents have been calibrated Otherwise you can confirm by long pressing the AUTO button on the User controller Calibrating exhaust vents 6 Repeat steps 3 to 5 inclusive for all exhaust vents 8 Verificat...

Page 13: ...span of 30 minutes remove and replace operations are ignored Removing a component 1 Activate Installer mode by long pressing 2 diagonal buttons on a paired control The LED will flash green rapidly 2...

Page 14: ...nication Print Slide the DVAM onto the 4 buses in the DucoBox and connect the cable to the Communication Print connector on the DucoBox PCB see drawing for correct connection 4 Connect the DUCO Wi Fi...

Page 15: ...15 WIFI PASSWORD 5 6 7 8 3 4...

Page 16: ...We inspire at www duco eu L2001033 B 26 08 2021...

Reviews: