12
4
Proceed now with the remaining supply vents. The flow rate from these other vents
must only be adjusted at the vents themselves. Adjusting vents will not alter the
flow from previously calibrated vents.
5
You will need to press the enter button ( ) on the DucoBox Energy Premium once
all supply vents have been calibrated. Otherwise you can confirm by long-pressing
the AUTO button on the User controller.
Calibrating
exhaust
vents
6
Repeat steps
3
to
5
inclusive for all exhaust vents.
8. Verification
The calibrated flow rates can be checked at the various vents once adjustment and calibration have been
completed. Do this by going into advanced mode and select “CALIBRATION → VERIFY HIGH LEVEL”. The
DucoBox Energy Premium will now ventilate for 30 minutes at its calibrated ventilation setting.