DualLite LiteGear Installation Instructions Manual Download Page 4

4

100.  Installation 

100.1  General Installation Requirements

CAUTION:

 

LiteGear cabinets are very heavy. Check to assure that the chosen location is capable of safely bearing the load.

Cabinet Size

: 18.375” W x 10.2” H x 8.25” D (46.6cm W x 25.9cm H x 21cm D)

Weight (including batteries): 70 lbs.

Install the LiteGear inverter system in a clean, cool, dry place with normal ventilation for human habitation. 
LiteGear inverter systems are UL Listed for 20°C to 30°C (+68°F to +86°F) operation. 
Battery performance and service life is maximized if the operating temperature is maintained at 25°C (77°F). 
The air around the unit must be clean, dust-free, and free of corrosive chemicals or other contaminants. Do not place 
the LiteGear inverter system or batteries in a sealed room or container. 

100.2  Cabinet Installation

CAUTION: 

Do not drill into the cabinet; drill filings may damage the unit and prevent it from operating. If additional or larger entry 

points are needed, use a chassis punch to enlarge the appropriate knockout. Do not add unnecessary knockouts. 

Remove the electronics module by removing the four screws on the right side of the cabinet.  (The inverter cabinet 
should be installed without the batteries inside.)

The LiteGear® units are supplied with two keyhole knockouts for wall mounting.  See Figure 100-1.  Necessary 
hardware to fasten the cabinet to the wall is to be supplied by the installing contractor.

Please refer to the following illustrations.

Install the input and output conduits.
AC Input service conductors and AC Output conductors must be run in separate conduits. LiteGear inverter system 
emergency output circuits must be installed in dedicated conduit systems and not shared with other electrical circuits 
as described in NEC 700-9(b). 

/$*6&5(:

.(<+2/(
.12&.287

)LJ

Cabinet should be empty before 
mounting. Use 1/4" lag screws 
through keyhole knockouts to mount 
cabinet to studs as shown

Summary of Contents for LiteGear

Page 1: ...Installation Instructions and User Manual 250 VA Inverter Power System...

Page 2: ...Battery acid can cause burns to skin and eyes If acid is spilled on skin or in the eyes flush with fresh water and contact a physician immediately 6 Equipment should be mounted in locations where it...

Page 3: ...rocedure 9 105 1 Sequence of Steps 9 105 2 Start Up Procedure Steps 9 106 System Verification 9 106 1 Initial System Status 9 106 2 System Transfer Test 9 200 Status Indicators 10 200 1 Indicators Pro...

Page 4: ...ill filings may damage the unit and prevent it from operating If additional or larger entry points are needed use a chassis punch to enlarge the appropriate knockout Do not add unnecessary knockouts R...

Page 5: ...eGear inverter system unit the unit can supply power from the AC line or from its batteries To avoid equipment damage or personal injury always assume that there is voltage inside the LiteGear inverte...

Page 6: ...s product with normally off lighting loads requires rewiring the circuit board to bypass an internal relay This process should only be performed by qualified personnel Refer to Fig 101 2 For 120VAC Op...

Page 7: ...tal wristwatches or other metal objects and jewelry Don t carry metal objects in pockets where the objects can fall onto the batteries or into the LiteGear inverter system Tools must have insulated ha...

Page 8: ...the red wire from the electronic module to the Positive Terminal of battery 1 and connect the blue wire to the Negative Terminal of battery 2 CAUTION Be careful to follow the bolt orientation shown i...

Page 9: ...sophisticated electronic backup power supply Care must be taken to follow the steps below in their exact sequence Failure to do so can result in possible equipment damage or failure 105 2 Start Up Pr...

Page 10: ...essing the test switch LED Status Indicator bi color green red LED Green Status Indicator During normal operation the green status LED will be constantly illuminated indicating the presence of AC powe...

Page 11: ...rt Code Faults Battery not connected battery string wiring is incomplete battery fuse FUSE1 on inverter pcb open Battery fault battery voltage below 24V following one minute test battery voltage below...

Page 12: ...unit After disconnecting the unit from the AC supply allow at least 5 minutes for capacitors to discharge before attempting service procedures If the service technician does not need to access the in...

Page 13: ...contain corrosive acids or caustic alkalis and toxic materials and can rupture or leak if mistreated Remove rings and metal wristwatches or other metal objects and jewelry Don t carry metal objects in...

Page 14: ...dispose of batteries in a fire the batteries could explode Do not open or mutilate batteries Released electrolyte is highly toxic and harmful to the skin and eyes CAUTION Batteries contain lead Many s...

Page 15: ...15 Notes...

Page 16: ...Hubbell Lighting Inc brand with representatives offices in principal cities throughout North America Copyright Hubbell Lighitng Inc All Rights Reserved Specifications subject to change without notice...

Reviews: