Installation – Terminal Description
40
4.1.3
MAGNETIC PICKUP, CAN AND EXPANSION
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
22
Magnetic pickup Positive
0.5mm²
AWG 20
Connect to Magnetic Pickup device
23
Magnetic pickup Negative
0.5mm²
AWG 20
Connect to Magnetic Pickup device
24
Magnetic pickup screen
Shield
Connect to ground at one end only
25
CAN port H
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
26
CAN port L
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
27
CAN port Common
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
28
DSENet exp
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
29
DSENet expansion -
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
30
DSENet expansion SCR
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
MSC
31
Multiset Comms (MSC) Link H
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
32
Multiset Comms (MSC) Link L
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
33
Multiset Comms (MSC) Link SCR
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
NOTE:- Terminal 34 to 38 are not fitted to the controller
NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that
the screen is earthed at one end ONLY.
NOTE:- Screened 120
Ω
Ω
Ω
Ω
impedance cable specified for use with CAN must be used for the
CAN link and the Multiset comms link.
DSE stock and supply Belden cable 9841 which is a high quality 120
Ω
Ω
Ω
Ω
impedance cable
suitable for CAN use (DSE part number 016-030)
NOTE:- When the module is configured for CAN operation, terminals 22, 23 & 24 should
be left unconnected. Engine speed is transmitted to the controller on the CAN link.
Refer to
Electronic Engines and DSE Wiring
for further information. Part No. 057-004.