ADJUSTABLE PARAMETERS
Front Panel Configuration Editor
(Factory default settings are shown in bold italicised text)
Section
Parameter as shown on display
Values
Display
Contrast
53%
Language
English, others.
Current Date and Time
hh:mm
Timers
LCD Page Timer
5m
Scroll Delay
2
s
Engine Pre Heat Timer
0s
Engine Crank Duration
10s
Engine Crank Rest Time
10s
Engine Safety On Delay
10s
Engine Smoke Limiting
0s
Engine Smoke Limiting Off
0s
Engine Warm Up Time
0s
Engine Cool Down Time
1m
Engine Speed Overshoot Delay
0s
Engine Failed To Stop
30s
Battery Under Voltage Warning Delay
1m
Battery Over Voltage Warning Delay
1m
Return Delay
30s
Generator Transient Delay
0s
Generator
Under Voltage Shutdown
184v
Under Voltage Pre-Alarm
196v
Nominal Voltage
230v
Over Voltage Pre-Alarm
265v
Over Voltage Shutdown
277v
Under Frequency Shutdown
40Hz
Under Frequency Pre-Alarm
42Hz
Nominal frequency
50Hz
Over Frequency Pre-Alarm
54Hz
Over Frequency Shutdown
57Hz
Full Load Rating
500A
kW Overload Trip
100%
Delayed Over current
Active
Delayed Over Current
100%
AC System
3 Phase 4 Wire
CT Primary
600A Power Cycle After Exit
CT Secondary
5A Power Cycle After Exit
Short Circuit Trip
200%
Earth CT Primary
500A
Earth Fault Trip
Active
Earth Fault Trip
10%
Transient Delay
0s
Gen Reverse Power Delay
2s
Gen Reverse Power
35kW
Engine
Oil Pressure Low shutdown
1.03bar
Oil Pressure Low Pre-Alarm
1.24bar
Coolant Temp High Pre-Alarm
90ºC
Coolant Temp High Electrical Trip
92ºC (When Enabled)
Coolant Temp High Shutdown
95ºC
Start Delay Off load
5s
Start Delay on load
5s
Start Delay Telemetry
5s
Pre Heat Timer
0s
Crank Duration
10s
Crank rest Time
10s
Safety On Delay
10s
Smoke Limiting
0s
Smoke limiting off
0s
Warm Up Time
0s
Cool Down Time
1m
Speed Overshoot Delay
0s
Speed Overshoot
0%
Fail To Stop Delay
30s
Battery Under Volts Warning
Active
Battery Under Volts Warning Delay
1m
Battery Under Volts Warning
10v
Battery Over Volts Warning
Active
Battery Over Volts Warning Delay
1m
Battery Over Volts Warning
30v
Charge Alternator Failure Warning
Active
Charge Alternator Failure Warning
6.0v
Charge Alternator Warning Delay
5s
Charge Alternator Failure Shutdown
Inactive
Charge Alternator Failure Shutdown
4.0v (When Enabled)
Charge Alternator Shutdown Delay
5s (When Enabled)
Droop %
Active, Inactive. Electronic engines only when droop is
enabled.
Front Panel Configuration Editor (continued)
Section
Parameter as shown on display
Values
Scheduler
Scheduler
Active, Inactive
Schedule On Load
Active , Inactive (Only Available When
Scheduler Is Active)
Schedule Period
Weekly, Monthly (Only Available When
Scheduler Is Active)
Schedule Time & Date Selection (1-16)
Press
to begin editing then
or
when selecting the different
parameters in the scheduler.
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
•
The ‘running’ editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
•
Press and hold the
button to enter the running editor.
ADJUSTABLE PARAMETERS (Running editor)
•
Enter the editor as described above.
•
Press the up
or down
buttons to cycle to the section you wish to view/change.
•
To Edit the parameter press the
button to enter edit mode. The parameter begins to flash to
indicate that you are editing the value.
•
Press the up
or down
buttons to change the parameter to the required value.
•
Press the
button to save the value. The parameter ceases flashing to indicate that it has been
saved.
•
To exit the editor at any time , press and hold the
button.
Running Editor
Section
Parameter as shown on display
Factory Settings
DISPLAY
Contrast
53%
Language
English