Front Panel Configuration
106
9.2 ADJUSTABLE PARAMETERS
Front Panel Configuration Editor. For descriptions of the parameters, you are referred to The DSE
series Configuration Suite Manual, DSE Part 057-160.
Section
Parameter As Shown On Display
Values
Display
Contrast
53%
Language
English, others.
Current Date and Time
hh:mm
Timers
LCD Page Timer
5m
Scroll Delay
2
s
Engine Pre Heat Timer
0s
Engine Crank Duration
10s
Engine Crank Rest Time
10s
Engine Safety On Delay
10s
Engine Smoke Limiting
0s
Engine Smoke Limiting Off
0s
Engine Warm Up Time
0s
Engine Cool Down Time
1m
Engine Speed Overshoot Delay
0s
Engine Failed To Stop
30s
Battery Under Voltage Warning Delay
1m
Battery Over Voltage Warning Delay
1m
Return Delay
30s
Generator Transient Delay
0s
Mains Transient Delay
2s
Mains transfer time
0.7s
Mains
Mains Under Voltage Alarm
184v
Mains Over Voltage Alarm
277v
Mains Under Frequency Alarm
45Hz
Mains over Frequency Alarm
55Hz
Mains Transient Delay
2s
CT Primary
600A
CT Secondary
5A
Mains kW Rating
345kW
Mains kVar Rating
258kW
Generator
Under Voltage Shutdown
184v
Under Voltage Pre-Alarm
196v
Nominal Voltage
230v
Over Voltage Pre-Alarm
265v
Over Voltage Shutdown
277v
Under Frequency Shutdown
40Hz
Under Frequency Pre-Alarm
42Hz
Nominal frequency
50Hz
Over Frequency Pre-Alarm
54Hz
Over Frequency Shutdown
57Hz
Full Load Rating
500A
kW Overload Trip
100%
Delayed Over current
Active
Delayed Over Current
100%
AC System
3 Phase 4 Wire
CT Primary
600A Power Cycle After Exit
CT Secondary
5A Power Cycle After Exit
Short Circuit Trip
200%
Earth CT Primary
500A
Earth Fault Trip
Active
Earth Fault Trip
10%
Transient Delay
0s
Gen Reverse Power Delay
2s
Gen Reverse Power
35kW
Engine
Oil Pressure Low shutdown
1.03bar
Oil Pressure Low Pre-Alarm
1.24bar
Coolant Temp High Pre-Alarm
90ºC
Coolant Temp High Electrical Trip
92ºC (When Enabled)
Coolant Temp High Shutdown
95ºC
Start Delay Off load
5s
Start Delay on load
5s
Start Delay Telemetry
5s
Pre Heat Timer
0s
Crank Duration
10s
Crank rest Time
10s
Safety On Delay
10s
Smoke Limiting
0s
Smoke limiting off
0s
Warm Up Time
0s
Cool Down Time
1m
Speed Overshoot Delay
0s
Speed Overshoot
0%
Fail To Stop Delay
30s
Battery Under Volts Warning
Active
Battery Under Volts Warning Delay
1m
Battery Under Volts Warning
10v
Battery Over Volts Warning
Active
Battery Over Volts Warning Delay
1m
Battery Over Volts Warning
30v
Charge Alternator Failure Warning
Active
Charge Alternator Failure Warning
6.0v
Charge Alternator Warning Delay
5s
Charge Alternator Failure Shutdown
Inactive
Charge Alternator Failure Shutdown
4.0v (When
Enabled)
Charge Alternator Shutdown Delay
5s (When
Enabled)
Droop %
Active, Inactive. Electronic engines only when
droop is enabled.
Scheduler
Scheduler
Active, Inactive
Schedule On Load
Active , Inactive (Only Available When Scheduler Is
Active)
Schedule Period
Weekly, Monthly (Only Available When Scheduler Is
Active)
Schedule Time & Date Selection (1-16)
Press
to begin editing then
or
when
selecting the different parameters in the
scheduler.