8.1 PROTECTIONS DISABLED
NOTE:- This feature is available in module versions 4 and above.
User configuration is possible to prevent Shutdown / Electrical Trip alarms from stopping the engine.
Under such conditions,
Protections Disabled
will appear on the module display to inform the operator of this status.
This feature is provided to assist the system designer in meeting specifications for “Warning only”, “Protections
Disabled”, “Run to Destruction”, “War mode” or other similar wording.
When configuring this feature in the PC software, the system designer chooses to make the feature either
permanently active, or only active upon operation of an external switch. The system designer provides this switch
(not DSE) so its location will vary depending upon manufacturer, however it normally takes the form of a key
operated switch to prevent inadvertent activation. Depending upon configuration, a warning alarm may be
generated when the switch is operated.
The feature is configurable in the PC configuration software for the module. Writing a configuration to the
controller that has “Protections Disabled” configured, results in a warning message appearing on the PC screen for
the user to acknowledge before the controller’s configuration is changed. This prevents inadvertent activation of
the feature.
8.1.1 INDICATION / WARNING ALARMS
Under Indication or Warning alarms :
•
The module operation is unaffected by the
Protections Disabled
feature. See sections entitled
Indications
and
Warnings
elsewhere in this document.
8.1.2 SHUTDOWN / ELECTRICAL TRIP ALARMS
NOTE:- The EMERGENCY STOP input and shutdown alarm continues to operate even when
Protections Disabled
has been activated.
Under Shutdown or Electrical Trip alarm conditions (excluding Emergency Stop) :
•
The alarm is displayed on the screen as detailed in the section entitled
Shutdown alarm
s elsewhere in this
document.
•
The set continues to run.
•
The load switch maintains its current position (it is not opened if already closed)
•
Shutdown Blocked
also appears on the LCD screen to inform the operator that the Protections Disabled
feature has blocked the shutdown of the engine under the normally critical fault.
•
The ‘shutdown’ alarm is logged by the controllers
Event Log (
if configured to log shutdown alarms) and
also logs that the Shutdown was prevented.
Summary of Contents for DSE7210
Page 41: ...DSE7200 7300 Series Operators Manual 41 4 3 1 7210 AUTOSTART CONTROLLER 3 phase 4 wire...
Page 42: ...DSE7200 7300 Series Operators Manual 42 4 3 2 7220 AMF CONTROLLER 3 phase 4 wire...
Page 121: ...This page is intentionally blank 121...
Page 122: ...This page is intentionally blank 122...
Page 128: ...DSECONTROL Gu a de Utilizaci n R pida DSE7000 057 101 Autor John Ruddock...