DSE7200 / 7300 Series Operators Manual
75
5.7 CONTROLS
Stop / Reset
This button places the module into its
Stop/Reset
mode. This will clear any alarm conditions for
which the triggering criteria have been removed. If the engine is running and the module is in Stop
mode, the module will automatically instruct the changeover device to unload the generator
(‘
Close
Generator
’
becomes inactive (if used))
. The fuel supply de-energises and the engine comes to a
standstill. Should a
remote start signal
be present while operating in this mode, a remote start will
not occur.
Manual
This mode allows manual control of the generator functions. Once in
Manual mode
the module will
respond to the start
button, start the engine, and run off load. If the engine is running off-load in
the
Manual mode
and a
remote start signal
becomes present, the module will automatically
instruct the changeover device to place the generator on load
(‘
Close Generator
’
becomes active (if
used))
. Upon removal of the
remote start signal
, the generator remains on load until either
selection of the
‘STOP/RESET’
or
‘AUTO’
modes.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this
manual.
Auto
This button places the module into its
‘Automatic’
mode. This mode allows the module to control
the function of the generator automatically. The module will monitor the
remote start
input and
mains supply status and once a start request is made, the set will be automatically started and
placed on load.
Upon removal of the starting signal, the module will automatically transfer the load from the
generator and shut the set down observing the
stop delay
timer and
cooling
timer as necessary. The
module will then await the next start event.
For further details, please see the more detailed
description of ‘Auto operation’ elsewhere in this manual.
5.7.1.1 TEST (DSE7220/DSE7320 ONLY)
This button places the module into its
‘Test’
mode. This allows an on load test of the generator.
Once in
Test mode
the module will respond to the start
button, start the engine, and run on load.
For further details, please see the more detailed description of ‘Test operation’ elsewhere in this
manual.
5.7.1.2 START
This button is only active in STOP/RESET
or MANUAL
mode.
Pressing this button in manual or test mode will
start the engine and run off load (manual) or on load
(test).
Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly
configured and fitted to a compatible engine ECU)
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test
feature/
When correctly configured and fitted to a compatible engine ECU, pressing this button in
STOP/RESET mode after pressing the START
button (to power the ECU) will cancel any
“passive” alarms on the engine ECU.
Summary of Contents for DSE7210
Page 41: ...DSE7200 7300 Series Operators Manual 41 4 3 1 7210 AUTOSTART CONTROLLER 3 phase 4 wire...
Page 42: ...DSE7200 7300 Series Operators Manual 42 4 3 2 7220 AMF CONTROLLER 3 phase 4 wire...
Page 121: ...This page is intentionally blank 121...
Page 122: ...This page is intentionally blank 122...
Page 128: ...DSECONTROL Gu a de Utilizaci n R pida DSE7000 057 101 Autor John Ruddock...