DSE7200 / 7300 Series Operators Manual
105
8.10 MAINTENANCE ALARM
Depending upon module configuration one or more
levels of maintenance alarm may occur based upon a
configurable schedule.
There are three maintenance alarms in the
DSE7200/DSE7300 series V3 and above, and one
level of maintenance alarm in prior versions.
Example 1
Screen capture from DSE Configuration Suite
Software showing the configuration of Maintenance
Alarm 1 and Maintenance Alarm 2.
When activated, the maintenance alarm can be either
a
warning
(set continues to run) or
shutdown
(running the set is not possible).
Resetting the maintenance alarm is normally actioned
by the site service engineer after performing the
required maintenance.
The method of reset is either by:
•
Activating a input that has been configured to maintenance x reset, where x is the number of the
maintenance alarm (1 to 3).
•
Pressing the maintenance reset button in the DSE Configuration Suite, Maintenance section.
•
Pressing and holding the stop button when the module’s display is on the maintenance alarm section.
(V9.x.x and above)
Example 2
Screen capture from DSE Configuration Suite
Software showing the configuration of a digital input
for Reset Maintenance Alarm 1.
Example 3
Screen capture from DSE Configuration Suite
Software showing the Maintenance Alarm Reset
‘button’ in the DSE Configuration Suite SCADA |
MAINTENANCE section.
Summary of Contents for DSE7210
Page 41: ...DSE7200 7300 Series Operators Manual 41 4 3 1 7210 AUTOSTART CONTROLLER 3 phase 4 wire...
Page 42: ...DSE7200 7300 Series Operators Manual 42 4 3 2 7220 AMF CONTROLLER 3 phase 4 wire...
Page 121: ...This page is intentionally blank 121...
Page 122: ...This page is intentionally blank 122...
Page 128: ...DSECONTROL Gu a de Utilizaci n R pida DSE7000 057 101 Autor John Ruddock...