6.5 AUTOMATIC MODE
NOTE:- If a digital input configured to
panel lock
is active, changing module modes will not be
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Activate auto mode be pressing the
pushbutton. An LED indicator beside the button confirms this action.
Auto mode will allow the generator to operate fully automatically, starting and stopping as required with no user
intervention.
6.5.1 WAITING IN AUTO MODE
If a starting request is made, the starting sequence will begin.
Starting requests can be from the following sources:
•
Mains supply out of limits (DSE7220/7320 only)
•
Activation of an auxiliary input that has been configured to
remote start on load
or
remote start off load.
•
Activation of the inbuilt exercise scheduler.
•
Instruction from external remote telemetry devices using the RS232 or RS485 interface
(DSE7310/DSE7320 only).
6.5.2 STARTING SEQUENCE
To allow for ‘false’ start requests such as mains brownouts, the
start delay
timer begins. There are individual start
delay timers for each of the different start request types.
Should all start requests be removed during the
start delay
timer, the unit will return to a stand-by state.
If a start request is still present at the end of the
start delay
timer, the fuel relay is energised and the engine will be
cranked.
NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start command via
CAN.
If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the
crank rest
duration after which the next start attempt begins. Should this sequence continue beyond the set number of
attempts, the start sequence will be terminated and the display shows
Fail to Start.
The starter motor is disengaged when the engine fires. Speed detection is factory configured to be derived from
the main alternator output frequency, but can additionally be measured from a Magnetic Pickup mounted on the
flywheel (Selected by PC using the 7000 series configuration software).
Additionally, rising oil pressure can be used to disconnect the starter motor (but cannot detect underspeed or
overspeed).
NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.
After the starter motor has disengaged, the
Safety On
timer activates, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.
Summary of Contents for DSE7210
Page 41: ...DSE7200 7300 Series Operators Manual 41 4 3 1 7210 AUTOSTART CONTROLLER 3 phase 4 wire...
Page 42: ...DSE7200 7300 Series Operators Manual 42 4 3 2 7220 AMF CONTROLLER 3 phase 4 wire...
Page 121: ...This page is intentionally blank 121...
Page 122: ...This page is intentionally blank 122...
Page 128: ...DSECONTROL Gu a de Utilizaci n R pida DSE7000 057 101 Autor John Ruddock...