INSTALLATION
SIREN AND ALARMS
FIND IT
Settings
Installation
Installer Code Access
Master Code Access
Siren and
Alarms
Setting
Default
Description
Disable Siren
Disabled
Turn internal piezo siren (and external siren, if connected) on or off.
UL Note: for UL/cUL the Siren is not allowed to be turned off to not
operate. This will not disable panics.
Siren Annunciation
Disabled
Panel siren pauses periodically to announce which locations have
triggered the alarm. UL Note: for UL/cUL this feature is not allowed
for Fire, CO, Burglar Alarm.
Fire Verification
Disabled
When disabled, fire alarm is triggered with a single fire event from
smoke detector. When enabled, panel requires two fire events from
smoke detector (one detector twice or two detects once each)
Severe Weather Siren
Warning
Enabled
When enabled, siren will sound when the panel receives a severe
weather alert. When disabled, panel will use severe weather chime.
UL NOTE: this functionality has not been evaluated by UL/cUL..
Alarm Transmission Delay
:30
Amount of time (in seconds) before panel will attempt call to
central station after an alarm event is triggered
When SIA Limits enabled: :15 to :45 seconds
When SIA Limits disabled: :05 to :254 seconds.
Note: maximum delay for UL/cUL shall be set for 30 sec.
Siren Timeout
5 min
Determine how long before siren stops sounding during an alarm
event (4 minutes to 8 minutes). For UL/cUL the minimum bell time
out shall be set to 5min.
Water/Freeze Siren
Enabled
When enabled, siren will sound when a water or freeze detector is
triggered. When disabled, the panel emits a “water” tone.
Allow Master Code To
Access Siren and Alarms
Disabled
Allow the master code to access these features and settings.
Note: not allowed for UL/cUL.