I n s t a l l a t i o n   a n d   W i r i n g :  

2 . 1 0   Z o n e   W i r i n g

9

End of Line Resistors  . . . . . . . . . . . . . . . . Section [013], Option [1]
Single End of Line Resistors  . . . . . . . . . . . Section [013], Option [2]

Double End of Line (DEOL) Resistors

Double end of line resistors allow the panel to determine
if the zone is in alarm, tampered or faulted. 
To enable panel detection of double end-of-line resistors,
programming section [013], option [1] must be OFF and
option [2] must be ON.

NOTE: 

If the double EOL supervision option is

enabled, all hardwired zones must be wired for double
EOL resistors, except for Fire and 24-hr Supervisory
zones.
Do not wire DEOL resistors on keypad zones.
Do not use DEOL resistors for Fire zones or 24-hr
Supervisory zones. Do not wire Fire zones to keypad
zone terminals if the DEOL supervision option is
selected.
This option can only be selected if Normally Closed
(NC) detection devices or contacts are being used. Only
one NC contact can be connected to each zone. 

The following chart shows zone status under certain con-
ditions:

End-of-Line Resistors  . . . . . . . . . . . . . . . . Section [013], Option [1]
Double End-of-Line Resistors  . . . . . . . . . . Section [013], Option [2]

Fire Zone Wiring - 4-wire Smoke Detectors

All zones defined as Fire 

(

see section ’Basic Programming

PWS Sect 3’

)

 must be wired according to the following

diagram:

For a complete description of how fire zones operate, see
section ’Basic Programming PWS Sect 3’

.

Fire Zone Wiring - 2-wire Smoke Detectors

If PGM2 has been programmed for 2-wire smoke detector
connection 

(

see section ’Basic Programming PWS Sect 3’

)

,

the detectors must be wired according to the following
diagram:

NOTE: 

If PGM2 is programmed for 2-wire smoke sup-

port, Jumper CON1 on the main board must be
removed.

For a complete description of how fire zones operate, see
section ’Basic Programming PWS Sect 3’

.

Keyswitch Zone Wiring

Zones may be programmed to be used as keyswitch arm-
ing zones and must be wired according to the following
diagram:

For a complete description of how keyswitch zones oper-
ate, see section ’Basic Programming PWS Sect 3’

.

LINKS1000 Supervisory (24-hr Supervisory)

When using the LINKS1000 cellular communicator, any
main board zone may be configured for LINKS1000 Super-
vision. Program this zone as zone type (09), 24-hr Supervi-
sory in section [001].
With a 24-hr Supervisory zone, if the LINKS1000 experi-
ences a trouble, the zone will be violated, causing the
panel to report the event to the central station. This type
of zone 

always 

requires a single EOL resistor

(5600

).Refer to LINKS 1000 

Installation Manual

 wiring

diagram for installation.

LINKS1000 Answer

If the LINKS1000 cellular commu-
nicator is being used a zone may
be configured for LINKS1000
Answer to allow downloading to
be performed in the event of tele-
phone line failure. When the
LINKS1000 receives a telephone
call it will activate the RING termi-

nal on the LINKS1000 circuit board. This terminal can be
used to violate a zone programmed as (24) LINKS1000
Answer 

(

see section ’Basic Programming PWS Sect 3’),

causing the panel to seize the telephone line and begin
communication with the downloading computer.
The zone programmed as LINKS1000 Answer ALWAYS
requires a single EOL resistor (5600

) and must be wired

according to the diagram above.

NOTE: 

The LINKS1000 Answer zone is only required

for downloading to the panel via the LINKS1000, or
for remotely connecting to the Escort5580(TC) module
via the LINKS1000.

NOTE: 

When using the LINKS1000, Busy Tone Detec-

tion must not be used.

Loop Resistance

Loop Status

0

 (shorted wire, loop shorted)

Fault

5600

 (contact closed)

Secure

Infinite (broken wire, loop open)

Tamper

11200

 (contact open)

Violated

Summary of Contents for PC5020 Power864

Page 1: ...ns information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5O2O PC5O2OCF Version 3 2 DLS 3 v1 3 and higher Now classified in accordance with ANSI SIA CP 01 2000 SIA FAR ...

Page 2: ...he system may fail to func tion as intended due to the failure of a component Inadequate Testing Most problems that would prevent an alarm system from operating as intended can be found by regular test ing and maintenance The complete system should be tested weekly and immediately after a break in an attempted break in a fire a storm an earthquake an accident or any kind of construction activity i...

Page 3: ... how a zone is defined according to the SIA specification for Contact ID If Automatic Contact ID is enabled see Appendix A for reporting codes that will be used for each zone type Keypad Buzzer When enabled and the system or Partition is in alarm all assigned keypad buzzers will follow the bell output When disabled the keypad buzzers will only sound for buzzer type alarms This option is off at def...

Page 4: ... 005 5 3 System Times Access to Entry Delays and Exit Delay for each partition and Bell Time Out for the system 009 011 5 3 Programmable Outputs Access to PGM Output programming for the main board PC5208 and PC5204 modules Output Attributes in Section in Sections 501 514 Partition Assignments in Section 551 564 014 Option 6 5 3 Audible Exit Beeps Enables beeps from the keypad for the duration of E...

Page 5: ...rd 20 5 2 Keypad Programming 20 5 3 Basic Programming 20 5 4 Advanced Programming 29 5 5 Partition Zone Programming 30 5 6 Communicator Programming 31 5 7 Downloading Options 40 5 8 Programmable Output Programming 41 5 9 International Programming 42 5 10 Module Programming 43 5 11 Special Installer Instructions 44 Section 6 Central Remote Station Fire Installation Instructions 46 6 1 Introduction ...

Page 6: ...iv PC5020 UL Wiring Diagram NOTE For ULC installations please refer to the ULC Wiring Diagram part 18006238 and the ULC Installation Information Sheet part 29002157 ...

Page 7: ... 32 user 1 system master 2 supervisor codes 2 duress 1 maintenance and 1 installer code Expandable to 64 zones Keypads with zone inputs available PC5508Z PC5516Z PC5532Z LCD5500Z and LCD5501Z Hardwired expansion available using the PC5108 8 zone expansion module the PC5100 addressable 32 zone expansion module and the PC5700 5720 fire module Wireless expansion available using the PC5132 wire less 3...

Page 8: ... zones PC5508 Z PC5516 Z PC5532 Z v2 00 and lower LCD5500 Z versions 2 x and lower LCD5501Z versions 1 x and lower PC5100 2 Wire Addressable Device Interface Module The PC5100 module is used to connect 2 wire addressable devices to the system Up to 32 2 wire addressable devices can be added to the system NOTE PC5100 v1 0 and lower modules can only sup port the first 32 zones on the PC5020 system P...

Page 9: ...an be used for ULC Listed non residential fire applications The PC5720 can also be used as an interface between the control panel and either a serial printer or a DVACS communications network NOTE The PC5700 v1 x and PC5720 v1 x enroll as two expander modules and use two supervisory slots NOTE Do not mix PC5700 v1 x and PC5720 v1 x and lower modules with PC5108 v2 0 and higher modules on the same ...

Page 10: ...an audio station next to a keypad Dimensions 208mm x 115mm x 18mm 8 2 x 4 5 x 0 25 approxi mately PC55BP2 Backplate Use this backplate when mounting an audio station next to a keypad In addition the backplate will allow you to mount a PC5108 zone expander module or the PC5208 8 low current output module Dimensions 208mm x 115mm x 18mm 8 2 x 4 5 x 0 7 approximately ...

Page 11: ... each module is properly supervised fol low the guidelines provided in section 2 8 Step 10 Programming the System Sections 4 5 Section 4 0 provides a complete description of how to pro gram the panel Section 5 0 contains complete descriptions of the various programmable features what options are available and how the options function The Programming Worksheets should be filled out completely befor...

Page 12: ...in incomplete transmis sions 2 3 Wire Routing for Power Non Power Limited All wiring entry points are designated by the arrows All circuits are classified UL installation power limited except for the battery leads which are not power limited A minimum 6 4mm separation must be maintained at all points between power limited and non power lim ited wiring and connections NOTE Wire entry for power limi...

Page 13: ...Refer to the Installation Instructions for the module for more infor mation NOTE Only jumpers J1 J2 and J3 determine the zone assignment for the module 2 7 Keypad Assignment There are 8 available slots for keypads LED and LCD5501Z keypads by default are assigned to slot 1 The LCD5500Z is assigned by default to slot 8 Keypads can each be assigned to a different slot 1 to 8 which offers two advantag...

Page 14: ... panel the module does not have enough power the PC5132 does not have any devices added 2 9 Removing Modules If a module is no longer required on the system the panel must be told to stop supervising the module To do this 1 Remove the module from the Keybus 2 Press 8 Installer Code to enter Installer Program ming 3 Press 902 to enable supervision The panel will auto matically search for all module...

Page 15: ...ption of how fire zones operate see section Basic Programming PWS Sect 3 Keyswitch Zone Wiring Zones may be programmed to be used as keyswitch arm ing zones and must be wired according to the following diagram For a complete description of how keyswitch zones oper ate see section Basic Programming PWS Sect 3 LINKS1000 Supervisory 24 hr Supervisory When using the LINKS1000 cellular communicator any...

Page 16: ...nd of line supervision connect the zone according to one of the configurations outlined in section 2 10 Zone Wiring NOTE End of line resistors must be placed on the device end of the loop not at the keypad NOTE Keypad zones do not support DEOL resistors Assigning Keypad Zones When using keypad zone inputs each input used must be assigned a zone number in Installer Programming First ensure that you...

Page 17: ...rogram boxes All other locations in the Section will remain unchanged If the key is pressed the panel will turn OFF the Ready light turn ON the Armed light and exit you from the Section 3 3 Programming Hexadecimal Data On occasion hexadecimal Hex digits may be required To program a Hex digit press the key The panel will enter Hex programming and Ready light will begin to flash The following table ...

Page 18: ... Emergency keys Fire Auxiliary or Panic to advance to the next digit When all the digits in a section have been viewed the panel will exit the section the Ready light will turn OFF and the Armed light will turn ON waiting for the next three digit programming section number to be entered Press the key to exit the section LCD Keypad When a programming section is entered the keypad will immediately d...

Page 19: ...tem at any time by entering 1 see section 1 Zone Bypassing or by using the Away function button If a delay zone is violated during the Exit Delay i e somebody leaves through the designated entry exit door all zones will be active after the Exit Delay expires The panel is now Away armed The Bypass light on the keypad will be off Other methods of Stay and Away arming are available see section Functi...

Page 20: ... can be viewed while armed using the LCD keypad provided the keypad is version 2 0 or later Older keypads will incorrectly display Fire Trou ble If using older LCD keypads program section 013 option 3 as OFF to ensure that Troubles are displayed correctly The various Troubles are described below Light Trouble 1 Service Required Press 1 to determine the specific Trouble Lights 1 8 will light up to ...

Page 21: ...e Master Code You can change the partition and attribute programming by following the instructions described below You cannot change Master Code partition or attribute programming The Master Code has all partitions and all attributes turned on except for the Bell Squawk on Arm ing Disarming attribute To program which partition s each code will work on 1 Enter 5 Master Code 8 to enter partition pro...

Page 22: ...e Auto arm Schedule menu See section 4 4 Global and Partition Keypad Operation for more information NOTE Only PKP LCD v2 0 or greater keypads support the 6 3 menu option 4 System Test When 4 is pressed the panel will perform the following sound the alarm output for two seconds light all lights and display pixels on the keypad sound the keypad buzzer for two seconds test the main panel PC5200 PC520...

Page 23: ...ing of any function key on any keypad may be changed to one of the options listed below see section 2 7 Keypad Assignment for instructions on changing function key programming 00 Null Key The key is not used and will perform no function when pressed 01 Select Partition 1 Provides an easy way to select partition 1 This is the same as pressing and holding the key then pressing and holding the 1 key ...

Page 24: ... 26 For Future Use 27 Select Partition 3 28 Select Partition 4 29 Select Partition 5 30 Select Partition 6 31 Select Partition 7 32 Select Partition 8 These keys provide users with an easy way to select one of the above partitions For example this is the same as press ing and holding the key then pressing and holding the 3 key to select partition 3 see section Global and Parti tion Keypad Operatio...

Page 25: ...nes to Partitions 555 560 PC5208 Sect 6 Communicator Programming 561 564 PC5204 301 304 Telephone Numbers Para 5 9 International Programming 310 System Account Code 700 Clock Adjust 311 318 Partition Account Code 701 First International Options Code 320 323 Alarm Reporting Codes Zones 01 64 702 Second International Options Code 324 327 Alarm Restoral Reporting Codes Zones 01 64 703 Delay between D...

Page 26: ...is tripped or if the F key is pressed during a delay NOTE This zone type should not be used for Commercial Fire applications 08 Standard 24 hr Fire Hardwired On alarm the bell output will sound to indicate that the fire loop has been activated If enabled the communicator will immediately transmit the alarm to the monitoring station NOTE DO NOT change the Zone attributes of Fire type zones from the...

Page 27: ... 9 armed a violation of this zone type will ini tiate Entry Delay 1 26 24 hr Non Alarm These zones are active at all times but do not cause an alarm and do not show up in alarm memory Zone Attributes such as Zone Bypassing and Door Chime affect the functionality of this zone A 24 hr Non alarm zone may be used for Zone Follower automation applications NOTE This zone type will be active in Walk Test...

Page 28: ...n partition Y will pulse Fire PGM with the Main Bell Silent alarms will be audible if either partition is in an audible alarm condition 02 Not Used For Future Use 03 Sensor Reset This output will normally be active This option is used to reset power for latching smoke detectors The output will deactivate for five seconds when the 7 2 command is entered see section 7 Command Output Functions The ke...

Page 29: ...nfigures the PGM1 terminal for operation with the LINKS1000 cellular alarm communicator 17 Away Armed Status This output will activate when the system is armed with the Stay Away zones activated 18 Stay Armed Status The output will activate when the system is armed with the Stay Away zones bypassed 19 Command Output 1 This output is activated by entering the 7 1 command The configuration of the co...

Page 30: ...ate the respective zone LED if the zone is in the Tamper or Fault states only the Trouble LED will be on OFF Tampers and Faults Show as Open The panel will illuminate the respective Zone LED if the zone is in the Tamper or Fault states The Trouble LED will also light 5 Auto arm Schedule Programming ON Auto arm Schedule in 6 The Auto arm schedules Sect 181 188 are accessible via 6 as well as Instal...

Page 31: ...pe alarms for the duration of Bell Time out or until an access code is entered 015 THIRD SYSTEM OPTION CODES Option Definition On Off Description 1 F Key ON F Key Enabled Pressing and holding the F key for 2 seconds will generate a Fire alarm The key pad will sound a set of 3 beeps to acknowledge the valid alarm and the bell or siren will pulse one second on one second off if option 8 of Section 0...

Page 32: ...ing any key on a blanked keypad will remove the blanking 5 Keypad Backlight ing ON Keypad Backlighting is Enabled All keypads on the system will have backlighting on all of the time OFF Keypad Backlighting is Disabled 6 Power Save Mode ON Power Save Mode Enabled If AC power fails all keypad lights including backlighting will be shut OFF The keypad lights will come back ON after a keypress Entry De...

Page 33: ...ours as they will be missed on the first Sunday in April Events programmed to occur between 0100 and 0200 will occur twice on the last Sunday in October 7 Periodic Camera Test ON Periodic Camera Test Enabled The panel will test all active cameras on the PC5108L every 30 minutes OFF Periodic Camera Test Disabled If this option is OFF the panel will only test all active cameras on the PC5108L upon e...

Page 34: ...w zone is open on the sys tem or not This Option is OFF at default 5 Keypad Buzzer Alarm ON Keypad Buzzer Follows Bell Enabled The keypad buzzers will follow the selected partition s bell activity OFF Keypad Buzzer Follows Bell Disabled The keypad buzzer will not follow all bell activity Only alarms designated to activate the keypad buzzer will do so This option is OFF at default 6 Cross Zoning Po...

Page 35: ...e Auto arm will be cancelled If a value between 001 and 255 is programmed then the Auto arm will be postponed for the corresponding number of minutes and the panel will resume normal operation The panel will also log the appropriate user log for the access code which postponed the arming When the postpone time expires the panel Auto arm Pre alert will be re initiated unless the parti tion is armed...

Page 36: ...1 198 No Activity Timer Partition 1 8 The timer will begin when a delay type zone assigned to the partition is restored The timer is stopped if any zone assigned to the partition is tripped or restored The timer will restart when a delay type zone is again restored When the timer expires the panel will sound the buzzers of all keypads assigned to the partition for the time pro grammed in Section 1...

Page 37: ...ng String This is a 6 digit Hex entry that is used to disable Call Waiting on a Call Waiting equipped phone line This is typically 70 in most areas Dialing this string before a phone number will disable Call Waiting for the duration of the call If this section is programmed not FF and Sec tion 382 Option 4 is ON the panel will dial this string in place of the first digit of the phone number Sectio...

Page 38: ...med period when using Police Code Burglary Not Verified this reporting code will be sent after the Burglary Verified Timer expires after a zone alarm occurs Alarm Cancelled this reporting code will be sent if a valid access code is entered during the Alarm Cancel window If a valid access code is entered during this window then the Alarm Cancelled event is logged and sent When the cen tral station ...

Page 39: ...ly Out put Module General System Supervisory Trouble a General System Supervisory Trouble reporting code will be transmitted if any module goes missing from the Keybus If the module is a zone expander the panel will also transmit the Zone Expander Supervisory Alarm Trouble reporting code 346 Maintenance Restoral Reporting Codes Battery Trouble Restoral the Battery Trouble Restoral reporting code w...

Page 40: ...l will transmit this reporting code when a TLM Trouble occurs on the PC5700 line 1 and or on line 2 PC5700 TLM 1 2 Restoral the panel will transmit this reporting code when a TLM Restoral occurs on the PC5700 line 1 and or line 2 350 Communicator Format Options Communicator Reporting Formats Each central station telephone number of the panel can be programmed to report using any one of the 5 forma...

Page 41: ...ogram 4A79 When programming reporting codes two digits must be entered If one digit reporting codes are to be used the sec ond digit must be programmed as a 0 If a 0 is to be transmitted substitute a Hex digit A for the 0 Examples 1 digit reporting code 3 program 30 2 digit reporting code 30 program 3A To prevent the panel from reporting an event program the reporting code for the event as 00 or F...

Page 42: ...value defines the number of attempts alarm and restoral pairs per zone that the communicator will make before it shuts down for that zone swinger shutdown Program 001 or 002 in this entry When programmed as 000 the communicator will shut down after 2 Alarm Restoral pairs Different limits can be programmed for Zone Alarms Zone Tampers and Maintenance signals After the panel has communicated the pro...

Page 43: ...timer will be ignored when the system is armed in the Away mode Zones that are bypassed in the 1 Bypass menu will not reset the timer If the system is programmed to monitor Closing Delinquency the timer will be programmed in days The timer will restart every time the system is disarmed Activity Closing Delinquency section 380 option 8 Communications Cancel Window After TX Delay expires and a zone ...

Page 44: ...for each Opening After Alarm code successfully reported OFF Opening After Alarm Keypad Ringback Disabled 2 Opening After Alarm Bell Ringback ON Opening After Alarm Bell Ringback Enabled When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number the bell will sound a series of 8 squawks to confirm to the end user that the Opening After Alarm code was se...

Page 45: ...INKS1000 options for the Communicator Call Direction Options for the event In addition the Call LINKS1000 as well as Land Line option must be selected The panel will call the LINKS1000 and then call the land line when reporting the selected event 8 Local Mode ON Local Mode Enabled The panel will always send events to the PC5108L module Downlook will not be initiated if requested OFF Local Mode Dis...

Page 46: ...r two rings then misses a ring 2 At this point the panel will start a timer 3 If the panel hears another ring before the Answering Machine Double Call Timer expires it will answer on the first ring of the second call The panel will immediately go on line and begin the download process unless the Call Back option is enabled If enabled the panel and computer will both hang up The panel will then cal...

Page 47: ...tput states do not occur after a loss and restoral of AC power If you program more than one PGM output as the same output type e g If PGM 1 and PGM 2 are both pro grammed as 19 Command Output 1 the settings for out put attributes 1 2 and 5 must be the same This does not apply to outputs programmed as types 09 and 10 NOTE Attribute 3 must be ON for PGM output option 16 Assigning Partitions to Progr...

Page 48: ...urs PGM Output Types 03 and 19 22 4 Output Options ON Output Pulsed The output will activate for the duration programmed in for the PGM Output Timer in Section 164 This default period is five seconds OFF Output On Off The output will toggle between on and off when the corresponding 7 command is entered PGM Output Types 19 22 5 Access Code Options ON Access Code Required for Activation OFF No Acces...

Page 49: ...If these tones are detected the communicator will disengage the phone line and try to place the call again following the Delay Between Dialing Attempts OFF Busy Tone Detection Disabled The communicator will use the standard dialing procedure for every attempt 7 Battery Current Charge ON High Current Battery Charge Approximately 650 700 mA OFF Standard Current Battery Charge Approximately 350 mA 8 ...

Page 50: ...or all partitions during the Walk Test regardless of programming To perform a Walk Test do the following 1 Enter Installer Programming 2 Enter Section 901 When any zone is violated the panel will activate the Bell Output for two seconds and log the event to the event buffer Check the event buffer to ensure that all zones and FAP keys are functioning properly NOTE If there is no zone activity on th...

Page 51: ...lts On occasion it may be necessary to default the main con trol panel or one of the modules that can be connected There are several different defaults available including defaulting the main control panel Escort5580 TC mod ule PC5132 wireless expander module PC5400 printer module and LINKS2X50 module NOTE Defaulting the main panel does not default the keypads See the Programming Worksheets Append...

Page 52: ...ich includes 16 EOL resistors 5 600Ω One black cabinet plug One green grounding strap Mounting hardware for the PC5020CF PCB One EOL resistor 2200Ω One 1000Ω resistor for bell supervision Minimum System Requirements for Commercial Fire Applications PC5020 CF System Components Central Station Fire Monitoring Service PC5020 control unit PC4050CR PC4050CRAR enclosure PC5700 fire module dual dialer or...

Page 53: ...he end of line resistor this will be indicated as a Zone Trouble Ground Fault resistance 40kΩ to earth ground indi cated as a Ground Fault Trouble on PC5700 zone 7 Typical Fire Devices used on this zone type are Heat Detectors fixed temperature and or rate of rise Fire alarm panel outputs such as Alarms and Troubles Manual pull stations 4 wire smoke detectors Standard Fire Operation When a Fire Mo...

Page 54: ...anel This detector may be connected to any PGM 1 4 The PGM must be programmed as Sensor Reset see Pro gramming Worksheets PGM2 can either be programmed for a 2 wire smoke detector or a 4 wire smoke detector but both detectors cannot be programmed concurrently on PGM2 For a wiring diagram see Appendix B 6 Sen sor Reset for 4 Wire Smoke Detectors 7 7 Two Wire Smoke Detector Zones PGM2 can be program...

Page 55: ...ill occur The Bell Time out if used will restart for a full timing period before automatic silencing The new alarm will be shown 8 5 Auto Scroll LCD Keypad Display When an alarm is initiated the Alarm and selected Trou ble conditions will be displayed on the system LCD key pad s If there is more than one Alarm or Trouble present simultaneously the keypad will continuously scroll through each event...

Page 56: ... the Fire Keys on any keypad are pressed for two seconds NOTE For commercial applications do not program the F key for keypads that are readily accessible by the public For more information regarding this key see the PC5020CF Installation Manual Section 5 3 Basic Programming 015 Third System Option Codes Option 1 System Maintenance Panel Battery Trouble This code will be sent when the control pane...

Page 57: ...ible alarm device power supply This may require duplicate protection armed by each partition Access to this protected area without causing an alarm will require that all partitions be disarmed In all cases described above the protected area for the control unit must be programmed as not bypassable Casual Users The installer should caution the user s not to give system information to casual users e...

Page 58: ...during any given armed to armed period incl 24 hr zones A R 1 4A BM 00 BV 00 328 Burglary Not Verified This reporting code will be sent after the Burglary Verified Timer expires after a zone alarm occurs A R 3 78 BG 00 328 Alarm Cancelled This reporting code will be sent if a valid access code is entered during the Alarm Cancel window A R 4 A6 BC 00 329 F Key Alarm Restoral Keypad fire alarm alarm...

Page 59: ... Lead In Downloading session start MA R 4 11 RB 00 347 DLS Lead Out Downloading session complete MA R 4 12 RS 00 347 Zone Fault Rest One or more zones have faults restored MA R 3 72 UT ZZ UJ ZZ 347 Delinquency Programmed amount of time days or hours for delinquency has expired without zone activity or without system being armed MA R 4 54 CD 00 347 Wireless Device Low Battery Trouble Rest Wireless ...

Page 60: ...er 1 59 Low Temp 1 32 Interior 1 61 Loss of Air Flow 1 33 24 hr Zone Definition SIA Auto Rep Codes Contact ID Auto Rep Codes Zone Alm Rest Zone Alm Rest Delay 1 BA ZZ BH ZZ 1 3A Delay 2 BA ZZ BH ZZ 1 3A Instant BA ZZ BH ZZ 1 3A Interior BA ZZ BH ZZ 1 3A Interior Stay Away BA ZZ BH ZZ 1 3A Delay Stay Away BA ZZ BH ZZ 1 3A Delayed 24 hr Fire FA ZZ FH ZZ 1 1A Standard 24 hr Fire FA ZZ FH ZZ 1 1A 24 h...

Page 61: ... Not to be removed by anyone except occupant This equipment should be installed in accordance with the National Fire Code ANSI NFPA 72 National Fire Protection Association Batterymarch Park Quincy MA 02269 Printed information describing proper installation operation testing maintenance evacuation planning and repair service is to be provided with this equipment This unit includes an alarm verifica...

Page 62: ...G AS SHOWN ABOVE IMPORTANT A minimum 1 4 6 4mm separation must be maintained at all points between battery primary AC wiring and all other wiring connections POWER LIMITED POWER LIMITED NON POWER LIMITED WARNING Do not route any wiring over circuit boards Maintain at least 1 25 4mm separation Cable Tie not provided Cable Tie To prevent wires from falling onto batteries secure them to the enclosure...

Page 63: ... be in the same room NOTE All circuits are Power Limited except AC and battery leads Voltage Barrier 80VA IMPORTANT A minimum of 1 4 6 4mm separation must be maintained at all points between power limited wiring and all other non power limited wiring and connections Wire entry for power limited wiring must be separate from non power limited wiring IMPORTANT A minimum of 1 4 6 4mm separation must b...

Page 64: ...facturer s literature when locating smoke detectors RM 1 POWER LOOP SUPERVISORY RELAY 12VDC 35mA MAXIMUM WHT 4 WIRE SMOKE DETECTORS Smoke Detector must be latching type such as DSC MN240 Series To reset smoke detectors enter 7 2 AUX PGM 2 1 Zone Input COM ALARM INITIATING LOOP RESISTANCE 100Ω PGM1 PGM2 PGM3 PGM4 PGM1 PGM2 PGM3 PGM4 NOTE For devices requiring more than 50mA use a relay DSC RM 1 or ...

Page 65: ...ke Detectors Enter an access code to reset smoke detectors Alarm Test Activate smoke detector or waterflow sensor according to manufacturer s testing instructions Bell and Communicator Test Enter 6 Access Code 4 on a system keypad Trouble Conditions Trouble conditions are indicated by The keypad Trouble light will turn ON The keypad buzzer will beep To view Trouble conditions Press 2 The keypad di...

Page 66: ...all in an emergency situation It must be able to do this even if other equipment telephone an swering system computer modem etc already has the telephone line in use To do so alarm dialing equipment must be connected to a properly installed RJ 31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line Proper installation is depicted in the fig...

Page 67: ...NOTES ...

Page 68: ...ith Power864 PC5132 v1 X Yes No support for Wireless Keys Pendants or Handheld Keypads Only the first 32 zones can be used as wireless zones PC5132 v2 X Yes No identified Wireless Keys support Only the first 32 zones can be used as wireless zones PC5132 v3 X Yes Only the first 32 zones can be used as wireless zones PC5200 Yes Fully compatible with Power864 PC5204 Yes Fully compatible with Power864...

Reviews: