New Features
PC5200 Support
The PC5020 v3.1 and higher supports the new PC5200 Power Supply module. See PC5200 Power Supply Output
Module, Pg 2.
PC5936 Support
The PC5020 v3.1 and higher supports the PC5936 15-station audio matrix module. See PC5936 Audio Interface
Module, Pg 3.
SIA FAR
SIA False Alarm Reduction has been incorporated in this version. See the Quick Reference Chart SIA-FAR on the fol-
lowing page.
No Activity Arming
(by Partition)
This feature enables the system (or partition) to arm if there is no zone activity for a programmed time period. See
sections [191]-[198] - No-Activity Timer (Partition 1-8), Pg 30.
Programmable
Auto-arm Pre-Alert
Timer
The Auto- arm Pre-alert Time is now programmable. The default value for this timer has been extended to 5 minutes.
See Section [199] - Auto-arming Pre-Alert Time, Pg 30.
Periodic Test
Transmission
Exception
With this feature enabled, the panel will not send a test transmission if there has been any transmission received by
the receiver within the programmed time. See Section [018] - Sixth System Option Codes, Option 1, Pg 27.
Cross Zoning
This feature requires two or more trips on a zone(s) specified as “cross zones” within a specified time before starting
an alarm sequence. The Cross Zone option is programmable by zone via Attribute 9. See Section [018], Sixth Sys-
tem Option Codes,Option 6, Pg 28.
True Automatic
Contact ID
When selecting Automatic Contact ID for reporting, the reporting code will represent how a zone is defined according
to the SIA specification for Contact ID. If Automatic Contact ID is enabled, see Appendix A for reporting codes that
will be used for each zone type.
Keypad Buzzer
When enabled and the system or Partition is in alarm, all assigned keypad buzzers will follow the bell output. When
disabled, the keypad buzzers will only sound for buzzer type alarms. This option is off at default. See Section [018] -
Sixth System Option Codes, Option 5, Pg 28.
New Zone Types
See Sections [001]-[004] - Zone Definitions, Pg 21.
Zone Type 27 - Delayed 24 Hour Waterflow Zone
Zone Type 28 - Instant 24 Hour Waterflow Zone
Zone Type 29 - Auto Verified Fire Zone
Zone Type 30 - Fire Supervisory Zone
Zone Type 31 - Day Zone
Waterflow Silence
Inhibit Option
This option affects the Instant Waterflow Zone and the Delay Waterflow Zone.
This option does
NOT
allow the user to silence alarms, manually, automatically, or by a system reset until all waterflow
zones are returned to their restored state. See Section [018] - Sixth System Option Codes, Option 4, Pg 28.
Verbal Door Chime
and Verbal Alarm
Support
This feature enables the Door Chime to verbally annunciate the Zone that has been violated instead of a series of
beeps. See Section [018] - Sixth System Option Codes, Option 2&3, Pg 33. This feature is only available when using
the
ESCORT5580 v3.0
, and the
PC5936 v1.0.
Refer to the Escort5580 v3.0 and PC5936 v1.0 Installation Manuals
for further information.
Loop Response
The PC5020 v3.1 and higher can configure any or all onboard zones for 36 ms Loop Response (see Section [030] -
Fast Loop Response, Pg 29).
T-Link
The PC5020 v3.2 supports the T-Link TCP/IP Network Communicator.