55
Appendix B: Wi ring Diagrams
B.1 PC5020CF Wiring Diagram (Ground Connection, Zone Circuits)
RED
BELL
+
AUX
–
AC
BLK YEL GRN
Z1
Z3
Z5
Z7
COM
COM
COM
COM
Z2
Z4
Z6
Z8
RING TIP R-1 T-1 EGND
PGM
1
3
2
4
RED
BLK
RED
BLK
BATTERY 2
BATTERY 1
12V 7.0Ah
Maximum battery
charge current
is 360 mA.
PGM 1: 50mA Max.*
PGM 2: 300mA Max.(supervised)
PGM 3: 50mA Max.
PGM 4: 50mA Max.
To +AUX
To +AUX
To +AUX
To +AUX
DEVICE
DEVICE
DEVICE
DEVICE
16.5VAC 37VA (min)
FTC Frost 3716
NOTE:
Refer to the Installation Manual
for other AC wiring options.
Do not connect to receptacle
controlled by a switch
IN
OUT
NO
ALM
-
OUT
+
-
IN
+
BLK
WHT
RED
GRN
EOLR-2
END OF LINE RESISTOR 5600
Ω
0.5W
Refer to installation guidelines in
Installation
Manual & detector manufacturer's literature
when locating smoke detectors.
RM-1 POWER LOOP SUPERVISORY RELAY
12VDC 35mA maximum
WHT
4-WIRE SMOKE DETECTORS
Smoke Detector must be latching type (DSC MN240 Series).
To reset smoke detectors, enter [ ] [7] [2].
✱
+ AUX
PGM 2
1
Zone Input
COM
ALARM
INITIATING
LOOP
RESISTANCE:
100
Ω
WARNING
High voltage. Disconnect
AC power and telephone
lines prior to servicing.
TYPICAL ZONE CIRCUITS
NORMALLY CLOSED
CONTACT WITH
END OF LINE
RESISTOR
ANY Z
TERMINAL
ANY COM
TERMINAL
NORMALLY OPEN
CONTACTS WITH
END OF LINE
RESISTOR
ANY Z
TERMINAL
ANY COM
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL
2 NORMALLY OPEN
CONTACT AND
2 NORMALLY CLOSED
CONTACT WITH
END OF LINE
RESISTOR
1 NORMALLY OPEN
CONTACT AND
1 NORMALLY CLOSED
CONTACT WITH
END OF LINE
RESISTOR
ANY Z
TERMINAL
ANY COM
TERMINAL
5600
Ω
5600
Ω
5600
Ω
5600
Ω
5600
Ω
5600
Ω
PGM CONNECTIONS (1-4)
IMPORTANT:
Minimum 6.4mm (0.25")
separation must be maintained between
RM-1 circuits and all other wiring.
RELAY OUTPUT
DSC
RM-1
RED
BLK
WHT YEL
GRN
COM N.C.N.O.
PGM2
LED INDICATOR
680
RESISTOR
(TYPICAL VALUE)
Ω
LED
INDICATOR
PGM
+ AUX
+ AUX
2
1
1
BELL / SIREN 12VDC 700 mA MAXIMUM
(Supervised for non-fire use only)
Supplementary Bell Circuit
PC-Link Connection
SI
SO
GROUND
CONNECTION
Tighten nut to break paint &
make a good connection to
the cabinet
Nut
Star washer
Lock washer
Lock washer
Ground wire
from building
electrical
installation
Nut
Cabinet
Bolt
UA186
2-WIRE SMOKE DETECTORS
AUX
YEL
GRN
BLK
RED
+
2200
END-OF-LINE
RESISTOR
EOLR-3
Ω
(
+)
(
-)
+ BELL -
1 PGM 2
Compatiblity Identifier: PC5-2
Maximum Operating Voltage: 13.75VDC
Maximum Circuit Resistance: 100
Ω (
total)
Do not
mix different models on the same circuit,
as the correct operation may be impaired.
Battery capacity for standby is
at least 24 hours. Recommended
Battery: DSC model BD7-12.
All terminals Class 2 Power Limited,
except battery leads.
60Hz
PRIMARY
120VAC
All zones 6.9VDC nominal (supervised)
For remote station use,
connect PS5350 with 60 hour
battery standby capacity
Same rating
as Battery 1
*420mA (max), 12VDC
Supervised
*420mA (max), 12VDC
Supervised
*300mA (max), 5VDC
Supervised
To PC5700
Fire Module
Connect to local phones
W
ARNING
Incorrect connections
may result in PTC
failure or improper
operation.
Refer to the 2-wire smoke detector compatibility chart in the manual.
DOUBLE EOL CIRCUIT
1 NORMALLY CLOSED
CONTACT WITH
5600
Ω
END OF LINE
RESISTORS
ANY Z
TERMINAL
ANY COM
TERMINAL
ALARM
CONTACT
NOTE:
Any device that will sink more than
50mA must be connected to PGM2.
Supervised
Max. Line Resistance
25.7 Ohms
NOTE:
The PC5020 is capable of a maximum of three
2-wire smoke detectors in the alarm condition.
PTC
SMOKE DETECTOR
POWER 12VDC
LATCHING 4-WIRE SMOKE
DETECTOR (DSC MN240 SERIES)
Zones 1-8 of PC5020 or
Zones 1-4 of PC5700
FCC Reg. No.: F53CAN-34330-AL-E REN=0.1B Plug Type: RJ-31X Made in Canada
This device complies with Parts 15 and 68 of the FCC rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
(a) The delay (power-up) (start-up) time marked on the
installation wiring diagram of the smoke detector or on the
installed smoke detector(s) is to be used.
TABLE 1
WARNING -
Not to be
removed by anyone except
occupant. This equipment
should be installed in
accordance with the National
Fire Code ANSI/NFPA 72
(National Fire Protection
Association, Batterymarch
Park, Quincy MA, 02269).
Printed information describing
proper installation, operation,
testing, maintenance,
evacuation planning, and
repair service is to be provided
with this equipment. This unit
includes an alarm verification
feature that will result in a
delay of the system alarm
signal from the indicated
circuits. The total delay
(control unit plus smoke
detectors) shall not exceed 60
seconds. No other smoke
detector shall be connected to
these circuits unless approved
by the local authority having
jurisdiction. For compliance
with UL-985, at least one
hardwired smoke detector is
required.
Compatible
signalling device:
Wheelock Model
34T-12-R (UL-Listed)
2-WIRE SMOKE
SINGLE ZONE EOL
2200
5%
Ω
RED
RED
RED
GOLD
5600
5%
Ω
BLUE
GOLD
GRN
RED
BELL CIRCUIT
GOLD
1000
5%
Ω
BR
WN
RED
BLK
RESISTOR
IDENTIFICATIONS
*NOTE:
AUX+ is shared between AUX+,
Keybus, (Red, Blk, Yel, Grn) and all PGM
outputs. Minimum system required: One
LCD5500Z keypad (85mA) and one
PC5700 (150mA)
or T-Link (150mA).
Available current for AUX+, Keybus &
PGM should total 180mA.
OBSERVE POLARITY
Name
Model
Compatibility ID
Max #
Base
DSC
MN220 /-R/-T/-RT
PS-220
30
None
System 2100AT
A
30
None
Sensor
2100TR
A
30
None
Sentrol
429AT or 521B/BXT
S09A
30
None
SW1 on
400 series,429C, 429CT
S10A
30
None
429CRT, 429CSST,
S11A
30
None
429CST
521CRXT S11A
30
None
521B, 521BXT, SW1 off
S10A
30
None
711U/UT, 712U,
S10A
30
None
721U/UD/UT
713-5U, 713-6U, 722U
S10A
30
None
731U, 731UD, 732U
S11A
30
None
Compatible 2-wire Smoke Detectors
Please see the 2-wire Smoke Detector Compatibility Chart (below) for a
list of 2-wire smoke detectors that have been listed as compatible with the
PC5020CF 2-wire smoke detection zone (PGM2).
NOTE: For PGM2 only.
Listed Services
1. Central Station Fire Monitoring
2. Remote Station Fire Monitoring
1mA
Applicable Standards
UL File No. S5596
UL864 -Control units for fire pro-
tective signaling systems
Not for field installations.
For max. loading, refer to the Battery
Calculation Charts part# 29005057
(2)12V 7Ah battery
(not supplied)
AC IN
ONLY
16V
AC
37VA
INSTALL BATTERY AND AC WIRING AS SHOWN ABOVE
Non-power
limited access
Power limited access
Power limited access
RED
BELL
+
AUX
–
AC
BLK YEL GRN
Z1
Z3
Z5
Z7
COM
COM
COM
COM
Z2
Z4
Z6
Z8
RING TIP R-1 T-1 EGND
PGM
1
3
2
4
PC5020 CONTROL PANEL WIRING DIAGRAM
UA186
Voltage Barrier
+
-
IMPORTANT:
A minimum of 1/4" (7mm)
separation must be maintained at all points
between power limited wiring and all other
non-power limited wiring and connections.
Wire entry for power limited wiring must be
separate from non-power limited wiring.
Refer to the PC5700 Installation
Instructions Part #29005063
Refer to the PC5020/PC5020CF Installation Manual P/N 29005907, Instruction Manual P/N
29005909. The PC5020 is UL Listed for limited energy installations per NEC Article 760.
Recognized limited energy cable should be used. Observe NEC wiring requirements and
local codes defined by the authority having jurisdiction. Printed information describing
proper installation, operation, testing, maintenance, evacuation planning, and repair service
is to be provided with this equipment. Security detection devices that require power from
the control panel must be UL Listed for the intended application and operate over the range
of 10.0 to 14.0 VDC. The DSC Bravo Series is a recommended UL Listed motion detector.
Temperature Range: 0˚C to 49˚C (32˚F to 120˚F)
Maximum Humidity: 85% relative humidity
Control panel is suitable for the following UL installations:
Grade AA Central Station and Grade AA Police Connect with high line security (using T-
Link to communicate to Sur-Gard MLR-IP receiver)
Household Fire and Grade A Household Burglary & Home
Health Care Signaling Equipment
Grade A Local
Grade B Central Station and Grade A Police Connect with basic line security
Grade C Central Station and Grade A Police Connect with basic line security
NOTE:
For ULC installations, please refer to the ULC Wiring Diagram part#18006238 and the ULC Installation
Information Sheet part#29002157.
Summary of Contents for PC5020 Power864
Page 67: ...NOTES ...