[096] SA Outgoing Local Port
Default (0C14/3093)
[097] SA Call Up IP
Default (000.000.000.000)
[098] SA Call Up Port
Default (0000)
[099] SA Password
Default (FFFFFFFF)
Ethernet Receiver 1 Options
[101] Ethernet Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account code is
used when transmitting heartbeat signals to the central station receiver. Signals received from the panel
will use the control panel account number. Valid range: 0000000001- FFFFFFFFFE. Programming all
0’s or all F’s will cause a module configuration trouble.
NOTE:
If Ethernet receiver 1 and cellular receiver 1 are programmed as the same receiver (IP and port
number are identical), Ethernet receiver 1 account code will be used.
[102] Ethernet Receiver 1 DNIS
Default (000000)
The Dialed Number Information Service (DNIS) is used in addition to the account code to identify the
communicator module at the central station. Valid range: 000000 - 099999. Value is entered as a leading
0 followed by the 5 digit DNIS. Format is Binary Coded Decimal (BCD).
NOTE:
Each Ethernet/cellular receiver must be programmed with a unique DNIS.
[103] Ethernet Receiver 1 Address
Default (127.000.000.001)
The default address enables the communicator to operate in Unattended Mode.
Unattended mode is used when a receiver is not available and the unit is required to perform DLS ses-
sions. Typically used where the customer programs the control panel daily due to access control and still
wants to receive alarms without buying extra hardware (receiver) or software.
NOTE:
When a valid IP address has been programmed, Ethernet receiver 1 is enabled and will com-
municate events over the Ethernet channel.
Ethernet receiver 1 and cellular receiver 1 may be configured to communicate to the same central station
receiver. To configure the device to operate using this common receiver mode functionality, program Eth-
ernet receiver 1 and cellular receiver 1, IP address and port number with identical values.
NOTE:
When operating in common receiver mode, Ethernet receiver 1 account code will be used for Eth-
ernet and cellular.
[104] Ethernet Receiver 1 UDP Remote Port
Default (0BF5/3061)
This Section determines the UDP remote port of Ethernet receiver 1. Valid range: 0000 - FFFF.
[105] Ethernet Receiver 1 UDP Local Port
Default (0BF4/3060)
Use this section to set the value of the UDP local outgoing port. Set the value of this port when the install-
ation is located behind a firewall and must be assigned a particular port number as determined by the
central station system administrator. Valid range: 0000 - FFFF.
[106] Ethernet Receiver 1 Domain Name
Default ( )
Enter the domain name as 32 ASCII characters.
Ethernet Receiver 2 Options
[111] Ethernet Receiver 2 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. The account code is
used when transmitting heartbeat signals to the central station receiver. Signals received from the con-
trol panel will use the control panel account number. Valid range: 0000000001- FFFFFFFFFE. Pro-
gramming all 0’s or all F’s will cause a module configuration Trouble (yellow LED=12 flashes).
25