DSC GS3060-RF Installation Manual Download Page 8

4

• Connect the GSM antenna to the radio module. Ensure that the connector is secure.
• Plug the battery harness into the connector on the PC board.

4. Apply power to the GS3060-RF:

• Connect the RED and BLACK leads of the battery harness to the battery.
• Connect the DC power source to +/- 12V terminals
• Allow the unit to power up and register with the network. Once powered, the green LEDs indicate

the signal strength. The bottom green LED must be on for the location to be acceptable. Please
refer to the 'Status LEDs' section for more information.

5. Power down the GS3060-RF by removing the DC power source and battery leads.

STEP 4 - Connect the GS3060-RF

1. Using the cabinet, mark the four screw locations. Drill the anchor screw holes.

NOTE: Check for cable conduits and water pipes before drilling.

2. Using anchor screws (not provided), mount the cabinet to the wall.
3. Run the cables through the cable entry [13] or through the cabinet knockouts.
4. Complete the connections on the terminal blocks [11].

NOTE: Ensure that power and Telco circuit connections are made only after the cabinet has been
secured to the building or structure, and has been connected to the protective earth ground.
Descriptions of the terminals can be found in the ‘Connecting the GS3060-RF’ section.

5. Reattach the front cover [1] securely to the cabinet.

NOTE: Please refer to Figure 2 at the end of this manual for wiring diagram.

(

1) Earth Ground -

This terminal must be connected to the Mains Earth, in order to comply with the

Telecommunications Network Safety Standards (Overvoltage Protection Requirements).

TIP (2) / RNG (3) External Telephone Line -

These terminals must be connected directly to the

incoming telephone line.

T1 (4) / R1 (5) Internal Telephone Line -

These terminals must be connected to the TIP and RING of

the control panel.

COM (6,14) Common -

This terminal is connected internally to Power Ground.

PGM1 (7), PGM2 (8), PGM3 (9), PGM4 (10) Programmable Open-collector Outputs -

These outputs

can be activated by programmed events. Refer to ‘Activating the Outputs’ for details. The maximum
current sink of each output must not exceed 50mA.

AUX+ (11) Auxiliary 12V Output -

+12V Output, 200mA PTC Protected.

NOTE: Electrical current drawn from this terminal is drawn directly from the power supply. This
must be added to the GS3060 current when determining the total draw on the host panel or
power supply. Jumper JP3 does not limit the electrical current available on this output.

Tamper (12-13) -

These terminals are connected in series to the Tamper switch [10] in Figure 1. They will

close when the cabinet is properly closed, and will open when the front cover is removed.

Z1-Z4 (15-16-17-18) Programmable Inputs

- These terminals can be set up to trigger events. Refer to

‘Inputs’ for details.

12V (19), COM (20) Device Power Supply

- These terminals must be connected to a rated power

supply. Once the connections are completed, connect the battery leads (Red and Black wires, [12] in
Figure 1) to a 12V, 7Ah battery.

Jumper JP3

JP3 ON

- Full power, including standby capacity, comes from the host panel or external power supply.

Supply must be capable of up to 700mA. The GS3060-RF battery must

not

be connected.

JP3 OFF

- Current limiting mode, the host panel or external supply provides standby current. Supply

must be capable of 120mA plus any current drawn from AUX+ terminal. GS3060-RF battery must be
installed for proper operation. Use only with supplied power supply.

NOTE: The power supply must have a minimum voltage of 13.5V to ensure a sufficient battery
charge. An example of a suitable power supply is the DSC Model ADP1310-NA with DC output
rated 13.8 VDC, 1Amp. This is to be used in conjunction with a 12V/7Ah rated battery for UL/ULC
listed residential installations.
NOTE: This mode of operation must not be used for ULC Listed Fire Monitoring installations.

CONNECTING THE GS3060

Summary of Contents for GS3060-RF

Page 1: ...E INSTALLATION MANUAL WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu facturer The entire manu...

Page 2: ......

Page 3: ...nd on terminal connections loosening of terminal connections damage of conductor insulation WARNING Never install this equipment during a lightning storm Instruct the end user to Not attempt to servic...

Page 4: ...nterrupted service Equipment Maintenance Facility If trouble is experienced with this equipment for repair or warranty information please contact the facility indicated below If the equipment is causi...

Page 5: ...ers Technical Specifications The input voltage to the GS3060 RF is drawn from the power adaptor model DSC ADP1310 NAU for USA and model DSC ADP1310 NA for Canada NOTE The power supply must be Class II...

Page 6: ...PGM2 19 20 DC IN 11 AUX 16 Z2 17 Z3 15 Z1 14 COM 10 PGM4 7 PGM1 6 COM 4 T1 5 R1 2 TIP 3 RNG 1 18 Z4 JP3 JP3 tie wrap OFF ON All circuits are classified for UL installations as Power Limited Class II P...

Page 7: ...Residential Fire and Burglary installations the GS3060 RF is listed as a sole means of communi cation or as a back up when used in conjunction with a POTS line dialer For UL Residential Fire installat...

Page 8: ...This terminal is connected internally to Power Ground PGM1 7 PGM2 8 PGM3 9 PGM4 10 Programmable Open collector Outputs These outputs can be activated by programmed events Refer to Activating the Outpu...

Page 9: ...Trouble condition exists This LED switches on when the interface switches to the GSM Network due to a Landline trouble condition This LED flashes slowly in the event of an incoming or outgoing voice...

Page 10: ...s the alarm and sends a command to the GS3060 RF to generate the corresponding 1400Hz Kiss off signal for a minimum of 800msec After the GS3060 RF generates a Kiss off signal it sends the next alarm o...

Page 11: ...IT ACTIVATION R552 RADIO XMITTER DISABLED 000 GSM INTERNAL BUFFER FULL E624 EVENT LOG OVERFLOW 000 FTC RESTORAL R354 FAILURE TO COMMUNICATE 000 Swinger Shutdown Swinger Shutdown is followed by a PSTN...

Page 12: ...The GS3060 will not show signal strength until the SIM is active Panel Programming the control panel should be programmed to communicate Contact ID exactly the same way it would be programmed to commu...

Page 13: ...rated at 13 8VDC 120mA minimum Ensure the GS3060 jumper J3 is OFF Two Flashes SIM Radio Trouble Ensure the SIM Card is inserted correctly and firmly Ensure the antenna cable is plugged securely into t...

Page 14: ...rt in this guide No signals are received at the central station but no trouble condition is displayed Ensure the control panel has a central station phone number programmed Ensure the control panel ha...

Page 15: ...r it typically takes less than an hour for the SIM card to be activated Checking SIM status Go to www connect24 com and login A search can be performed for a specific account and its current status SI...

Page 16: ...quired for normal long term operation Telephone Line Connection Supervision Relay RM1 UL Installations RM1C ULC Installations WARNING Incorrect connections may result in PTC failure or improper operat...

Page 17: ...2 COM 20 Z1 12 AUX PGM 3 PGM 1 13 PGM 4 COM TAMPER GS3060 PGM 3 DC IN KSAD1380100W1US Power Adaptor NOTES 1 Program the Zone Point as Supervisory type with keypad only annunciation when in Alarm Do NO...

Page 18: ...agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DS...

Page 19: ...s to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be credited or replaced at DS...

Page 20: ...LYHO HQIRUFH LWV LQWHOOHFWXDO SURSHUW ULJKWV WR WKH IXOOHVW H WHQW RI WKH ODZ LQFOXGLQJ SXUVXLW RI FULPLQDO SURVHFXWLRQ ZKHUHYHU QHFHVVDU OO WUDGHPDUNV QRW RZQHG E 7 FR QWHUQDWLRQDO WG DUH WKH SURSHUW...

Reviews: