DSC GS3060-RF Installation Manual Download Page 6

2

 Figure 1 - Parts

IDENTIFICATION OF PARTS

Table 1: Parts 

Parts

1

Metal Casing

2

GSM Antenna

3

GSM Antenna Mounting Hardware

4

Anchor Screw Holes (3mm)

5

GSM Antenna Connector

6

SIM Card

7

Status LEDs (see page 5)

8

JP3 Current Limitation Jumper (refer to Ratings Section)

9

PC-Link Connector

10

Tamper Switch

11

Terminal Blocks

12

Battery Leads

13

Cable Entry

14

Earth Ground Wire

15

12V - 1.2Ah Battery

16

ADP-1310-NAU/ADP-1310-NA Power Adaptor

17

GSM Radio Module

18

SIM Card Holder

LE

LI

-

O1

M

O2 O3 O4 +OC AS

M L1 L2 L3 L4 +12V-

LOCK

OPEN

18

17 

9

10

11

13
12

15

14

16 (not shown)

12     13

TAMPER

9

PGM3

8

PGM2

19     20

+

 DC IN 

-

11

AUX+

16

Z2

17

Z3

15

Z1

14

COM

10

PGM4

7

PGM1

6

COM

4

T1

5

R1

2

TIP

3

RNG

1

18

Z4

JP3 

JP3

tie wrap

OFF ON

All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the bat-
tery leads which are not power limited. Do not route any wiring over circuit boards. Maintain at least 1” 
(25.4mm) separation. A minimum 1/4” (6.4mm) of separation must be maintained at all points between 
Power Limited wiring and all other non-Power Limited wiring. Route wires as indicated above. 

DG009554

 

GS3060-RF

NOTE: 

For UL/ULC installa-

tions, connections between 
the alarm control panel out-
puts (telephone interface 
Tip/Ring, output relay con-
tacts) and GS3060-RF 
inputs (Tip/Ring, Z1-Z4) 
shall be run in a mechanical 
protective conduit within 
20ft (6m) of one another and 
in the same room. 

Summary of Contents for GS3060-RF

Page 1: ...E INSTALLATION MANUAL WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu facturer The entire manu...

Page 2: ......

Page 3: ...nd on terminal connections loosening of terminal connections damage of conductor insulation WARNING Never install this equipment during a lightning storm Instruct the end user to Not attempt to servic...

Page 4: ...nterrupted service Equipment Maintenance Facility If trouble is experienced with this equipment for repair or warranty information please contact the facility indicated below If the equipment is causi...

Page 5: ...ers Technical Specifications The input voltage to the GS3060 RF is drawn from the power adaptor model DSC ADP1310 NAU for USA and model DSC ADP1310 NA for Canada NOTE The power supply must be Class II...

Page 6: ...PGM2 19 20 DC IN 11 AUX 16 Z2 17 Z3 15 Z1 14 COM 10 PGM4 7 PGM1 6 COM 4 T1 5 R1 2 TIP 3 RNG 1 18 Z4 JP3 JP3 tie wrap OFF ON All circuits are classified for UL installations as Power Limited Class II P...

Page 7: ...Residential Fire and Burglary installations the GS3060 RF is listed as a sole means of communi cation or as a back up when used in conjunction with a POTS line dialer For UL Residential Fire installat...

Page 8: ...This terminal is connected internally to Power Ground PGM1 7 PGM2 8 PGM3 9 PGM4 10 Programmable Open collector Outputs These outputs can be activated by programmed events Refer to Activating the Outpu...

Page 9: ...Trouble condition exists This LED switches on when the interface switches to the GSM Network due to a Landline trouble condition This LED flashes slowly in the event of an incoming or outgoing voice...

Page 10: ...s the alarm and sends a command to the GS3060 RF to generate the corresponding 1400Hz Kiss off signal for a minimum of 800msec After the GS3060 RF generates a Kiss off signal it sends the next alarm o...

Page 11: ...IT ACTIVATION R552 RADIO XMITTER DISABLED 000 GSM INTERNAL BUFFER FULL E624 EVENT LOG OVERFLOW 000 FTC RESTORAL R354 FAILURE TO COMMUNICATE 000 Swinger Shutdown Swinger Shutdown is followed by a PSTN...

Page 12: ...The GS3060 will not show signal strength until the SIM is active Panel Programming the control panel should be programmed to communicate Contact ID exactly the same way it would be programmed to commu...

Page 13: ...rated at 13 8VDC 120mA minimum Ensure the GS3060 jumper J3 is OFF Two Flashes SIM Radio Trouble Ensure the SIM Card is inserted correctly and firmly Ensure the antenna cable is plugged securely into t...

Page 14: ...rt in this guide No signals are received at the central station but no trouble condition is displayed Ensure the control panel has a central station phone number programmed Ensure the control panel ha...

Page 15: ...r it typically takes less than an hour for the SIM card to be activated Checking SIM status Go to www connect24 com and login A search can be performed for a specific account and its current status SI...

Page 16: ...quired for normal long term operation Telephone Line Connection Supervision Relay RM1 UL Installations RM1C ULC Installations WARNING Incorrect connections may result in PTC failure or improper operat...

Page 17: ...2 COM 20 Z1 12 AUX PGM 3 PGM 1 13 PGM 4 COM TAMPER GS3060 PGM 3 DC IN KSAD1380100W1US Power Adaptor NOTES 1 Program the Zone Point as Supervisory type with keypad only annunciation when in Alarm Do NO...

Page 18: ...agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DS...

Page 19: ...s to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be credited or replaced at DS...

Page 20: ...LYHO HQIRUFH LWV LQWHOOHFWXDO SURSHUW ULJKWV WR WKH IXOOHVW H WHQW RI WKH ODZ LQFOXGLQJ SXUVXLW RI FULPLQDO SURVHFXWLRQ ZKHUHYHU QHFHVVDU OO WUDGHPDUNV QRW RZQHG E 7 FR QWHUQDWLRQDO WG DUH WKH SURSHUW...