3
This equipment GS3060-RF is fixed and shall be installed by Service Persons only (Service Person is
defined as a person having the appropriate technical training and experience necessary to be aware of
hazards to which that person may be exposed in performing a task, and of measures available to
minimize the risks to that person or other persons). It shall be installed and used within an environment
that provides the pollution degree max 2, over voltages category II, in non-hazardous, indoor locations
only. This manual shall be used with the Installation Manual of the relevant alarm control panel. All
instructions specified within that manual must be observed.
Description
This GS3060-RF manages transmissions to a central station and can simulate the landline in the event of
trouble (e.g., landline down) or even substitute the landline completely in areas where the GSM service
is provided and a landline is not available.
The GS3060-RF has the capability of communicating alarm signals via the GPRS data network. This
capability ensures a fast, reliable path to central stations equipped with a Sur-Gard System III, System II
or System I receiver. By connecting a GS3060-RF to a control panel's standard PSTN interface, tele-
phone-based Contact ID signals are decoded and seamlessly routed through the GPRS network to any
of the compatible receiver options.
The performance of the GS3060-RF depends greatly on GSM network coverage. Therefore, it should not
be mounted without first performing placement tests to determine the best location for reception
(minimum of one green LED ON). Optional antenna kits – GS15/25/50-ANT (15ft/4.6m, 25ft/7.6m or
50ft/15.2m) – are available.
The GS3060-RF requires enrollment with CONNECT 24 to operate. Dealer application forms and
additional information on the CONNECT 24 Voice Response Unit (VRU) and web user interface can be
found at www.connect24.com, or at the following telephone numbers:
USA 1-888-251-7458 CANADA 1-888-955-5583
For UL Residential Fire and Burglary installations, the GS3060-RF is listed as a sole means of communi-
cation or as a back up when used in conjunction with a POTS line (dialer). For UL Residential Fire
installations, the GS3060-RF has provisions for 24-hour standby power.
For ULC Residential Fire and Burglary installations the GS3060-RF is listed as a sole means communica-
tion or as a back up when used in conjunction with a POTS line (dialer).
NOTE: With the current limiter active, there is a risk of discharging the GS3060-RF battery when
transmission frequency is high. The back up battery must always be connected to the device
when the current limiter is enabled.
CONNECT 24 Enrollment Information
Only authorized dealers can enroll a GS3060-RF with CONNECT 24. Dealer application forms and
additional information on the CONNECT 24 Voice Response Unit can be found at the CONNECT 24 web
site www.connect24.com. Please contact CONNECT 24 at the number below for assistance:
USA 1-888-251-7458 CANADA 1-888-955-5583
NOTE: Steps 1 and 2 should be completed before turning on the GS3060-RF unit.
NOTE: Before inserting or removing the SIM card, please ensure the unit is turned off.
STEP 1 - Activate Your SIM Card
Your SIM card must be activated with Connect 24 prior to use. Please call the Voice Response Unit (VRU)
at least 24 hrs prior to installation at 1-866-910-3865.
STEP 2 - Initialize the GS3060-RF with Connect 24
Call the VRU at the toll-free number. Follow the voice prompts and enter your profile number, installer
ID number, installer PIN number and central station number. Ensure that all information is available and
at hand before calling the VRU. This information can be found in your VRU Enrollment Package.
STEP 3 - Determine the Best Location (SIM must be activated for this step)
1. Unscrew the four screws securing the front panel to the cabinet. Remove the front panel.
2. Fit the GSM antenna [2]. Ensure the GSM antenna mounting hardware is fastened securely [3].
3. Install the circuit board:
• From behind the cabinet, insert a standoff (supplied with hardware pack) into each of 4 mounting
holes and press into position.
• Press the circuit board onto the standoffs.
INSTALLING THE GS3060
Summary of Contents for GS3060-RF
Page 2: ......