9

Yellow Light 

Status

What It Means: GSM Status/Communication Indicator

Yellow Light

ON

• When used as the primary communicator, the yellow light will always be

ON

• When used as a backup communicator, the yellow light will be ON when

there is a no phone line connected to the GS3060 TIP and RING, or the line
voltage goes below 2.8VDC.

Yellow Light

OFF

• Indicates a good phone line is connected to the GS3060. (more than 2.8

VDC detected across the GS3060 TIP and RING terminals).

Yellow Light

FLASHING

• The yellow light will flash one time when the GS3060 transmits a signal

and two times when a kisoff is received.

Red Light 

Status

What it means:

Trouble Status 

Trouble Status - Troubleshooting Steps

One Flash

GS3060 Low Battery

• Measure the battery under load and verify it is

charged to at least 12.5 VDC. If not, wait at least 1
hour for the battery to charge

• Remove the battery and measure the voltage across

the two battery leads; the voltage should be at least
13.5 VDC

• Verify the input DC supply is rated at 13.8VDC @

120mA minimum

• Ensure the GS3060 jumper J3 is OFF

Two Flashes

SIM/Radio Trouble

• Ensure the SIM Card is inserted correctly and firmly
• Ensure the antenna cable is plugged securely into the

radio connector

• Ensure the power source connected to the GS3060 is

providing 13.8VDC @ 120mA and that the battery is
fully charged

Three
Flashes

GSM Network Problem

• Ensure the SIM card has been activated
• The antenna cable should be plugged securely into

the radio connector

• Ensure there is good signal strength (at least one

green light ON)

• Verify the installation area is not experiencing a net-

work outage

Four Flashes

Insufficient Signal
Strength

• Ensure there is good signal strength (at least one

GS3060 green light ON)

• Ensure the antenna cable is plugged securely into the

radio connector

Five Flashes

Configuration Trouble

• Ensure the SIM card is activated

Six Flashes

Receiver Not Available

• Contact the monitoring station to verify that the

GS3060 programming is correct (port, IP address,
DNIS).

• Contact your central station to verify they are not

experiencing any receiver issues

Seven
Flashes

DC Supply Trouble

• Ensure the power source connected to the GS3060 is

providing 13.8VDC @ 120mA

Summary of Contents for GS3060-RF

Page 1: ...E INSTALLATION MANUAL WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu facturer The entire manu...

Page 2: ......

Page 3: ...nd on terminal connections loosening of terminal connections damage of conductor insulation WARNING Never install this equipment during a lightning storm Instruct the end user to Not attempt to servic...

Page 4: ...nterrupted service Equipment Maintenance Facility If trouble is experienced with this equipment for repair or warranty information please contact the facility indicated below If the equipment is causi...

Page 5: ...ers Technical Specifications The input voltage to the GS3060 RF is drawn from the power adaptor model DSC ADP1310 NAU for USA and model DSC ADP1310 NA for Canada NOTE The power supply must be Class II...

Page 6: ...PGM2 19 20 DC IN 11 AUX 16 Z2 17 Z3 15 Z1 14 COM 10 PGM4 7 PGM1 6 COM 4 T1 5 R1 2 TIP 3 RNG 1 18 Z4 JP3 JP3 tie wrap OFF ON All circuits are classified for UL installations as Power Limited Class II P...

Page 7: ...Residential Fire and Burglary installations the GS3060 RF is listed as a sole means of communi cation or as a back up when used in conjunction with a POTS line dialer For UL Residential Fire installat...

Page 8: ...This terminal is connected internally to Power Ground PGM1 7 PGM2 8 PGM3 9 PGM4 10 Programmable Open collector Outputs These outputs can be activated by programmed events Refer to Activating the Outpu...

Page 9: ...Trouble condition exists This LED switches on when the interface switches to the GSM Network due to a Landline trouble condition This LED flashes slowly in the event of an incoming or outgoing voice...

Page 10: ...s the alarm and sends a command to the GS3060 RF to generate the corresponding 1400Hz Kiss off signal for a minimum of 800msec After the GS3060 RF generates a Kiss off signal it sends the next alarm o...

Page 11: ...IT ACTIVATION R552 RADIO XMITTER DISABLED 000 GSM INTERNAL BUFFER FULL E624 EVENT LOG OVERFLOW 000 FTC RESTORAL R354 FAILURE TO COMMUNICATE 000 Swinger Shutdown Swinger Shutdown is followed by a PSTN...

Page 12: ...The GS3060 will not show signal strength until the SIM is active Panel Programming the control panel should be programmed to communicate Contact ID exactly the same way it would be programmed to commu...

Page 13: ...rated at 13 8VDC 120mA minimum Ensure the GS3060 jumper J3 is OFF Two Flashes SIM Radio Trouble Ensure the SIM Card is inserted correctly and firmly Ensure the antenna cable is plugged securely into t...

Page 14: ...rt in this guide No signals are received at the central station but no trouble condition is displayed Ensure the control panel has a central station phone number programmed Ensure the control panel ha...

Page 15: ...r it typically takes less than an hour for the SIM card to be activated Checking SIM status Go to www connect24 com and login A search can be performed for a specific account and its current status SI...

Page 16: ...quired for normal long term operation Telephone Line Connection Supervision Relay RM1 UL Installations RM1C ULC Installations WARNING Incorrect connections may result in PTC failure or improper operat...

Page 17: ...2 COM 20 Z1 12 AUX PGM 3 PGM 1 13 PGM 4 COM TAMPER GS3060 PGM 3 DC IN KSAD1380100W1US Power Adaptor NOTES 1 Program the Zone Point as Supervisory type with keypad only annunciation when in Alarm Do NO...

Page 18: ...agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DS...

Page 19: ...s to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be credited or replaced at DS...

Page 20: ...LYHO HQIRUFH LWV LQWHOOHFWXDO SURSHUW ULJKWV WR WKH IXOOHVW H WHQW RI WKH ODZ LQFOXGLQJ SXUVXLW RI FULPLQDO SURVHFXWLRQ ZKHUHYHU QHFHVVDU OO WUDGHPDUNV QRW RZQHG E 7 FR QWHUQDWLRQDO WG DUH WKH SURSHUW...

Reviews: