Installing the 3G3070
4
STEP 1 - Determine the Best Signal Location
1. Unscrew the four screws securing the front panel to the cabinet. Remove the front panel.
2. Fit the 3G antenna [figure 1, item 2]. Ensure the 3G antenna mounting hardware is fastened
securely [figure 1, item 3].
3. Attach the 3G radio module with the 3G antenna connector. Ensure that the connector is secure.
4. Slide the SIM card holder to the left, in the direction labeled "OPEN" on the SIM card holder.
5. Insert the SIM card into the SIM card holder. The notch on the SIM card should face towards the
LEDs.
6. Once the card is properly seated in the connector, press down and
slide
it into the "LOCK" position
as indicated on the SIM card holder.
7. Turn on the 3G3070 and check the signal strength.
a) Connect the battery to the RED and BLK battery leads.
b) Connect the DC power source to +/- 12V terminals.
8. Allow the unit to power up.
NOTE: The green LEDs will indicate the signal strength. The bottom green LED must be
ON (solid)
for
the location to be acceptable. Please refer to the ‘Status LEDs’ section for more information.
9. Power down the 3G3070 by removing the DC power source and battery leads.
STEP 2 - Connect the 3G3070
1. Using the cabinet, mark the four screw locations. Drill the anchor screw holes.
NOTE: Check for cable conduits and water pipes before drilling.
2. Using anchor screws (not provided), mount the cabinet to the wall.
3. Run the cables through the cable entry [figure 1, item 13] or through the cabinet knockouts.
4. Complete the connections on the terminal blocks [figure 1, item 11].
NOTE: Ensure that power and Telco circuit connections are made only after the cabinet has been
secured to the building or structure, and has been connected to the protective earth ground.
Descriptions of the terminals can be found in the ‘Connecting the 3G3070’ section.
5. Reattach the front cover [figure 1, item 1] securely to the cabinet.
Connecting the 3G3070
NOTE: Please refer to Figure 4 at the end of this manual for wiring diagram.
(
1) Earth Ground -
This terminal must be connected to the Mains Earth, in order to comply with the
Telecommunications Network Safety Standards (Overvoltage Protection Requirements).
TIP (2) / RNG (3) External Telephone Line -
These terminals must be connected directly to the
incoming telephone line.
T1 (4) / R1 (5) Internal Telephone Line
-
These terminals must be connected to the TIP and RING of
the control panel.
COM (6,14) Common
-
This terminal is connected internally to Power Ground.
PGM1 (7), PGM2 (8), PGM3 (9), PGM4 (10) Programmable Open-collector Outputs -
These
outputs can be activated by programmed events. Refer to ‘Activating the Outputs’ for details. The
maximum current sink of each output must not exceed 50mA.
AUX+ (11) Auxiliary 12V Output -
+12V Output, 200mA PTC Protected.
NOTE: Electrical current drawn from this terminal is drawn directly from the power supply. This
must be added to the 3G3070 current when determining the total draw on the host panel or
power supply. Jumper JP3 does not limit the electrical current available on this output.
Tamper (12-13) -
These terminals are connected in series to the Tamper switch [10]. They will close
when the cabinet is properly closed, and will open when the front cover is removed.
Z1-Z4 (15-16-17-18) Programmable Inputs
- These terminals can be set up to trigger events. Refer to
‘Inputs’ for details.
12V (19), COM (20) Device Power Supply
- These terminals must be connected to a rated power
supply. Once the connections are completed, connect the battery leads (Red and Black wires, [12] in
Figure 1) to the supplied battery.
Summary of Contents for 3G3070
Page 2: ......