7.3.4 Connection to an existing chimney
The appliance can be connected to an existing chimney (C91). A 100 mm diameter flexible SS pipe is placed in the
chimney for discharging flue gases. The surrounding space is used as combustion air supply. Use the DRU spacer here.
Place this spacer every three metres.
In case of an appliance connection of ø200/130 mm, 0.8 metres of concentric system must first be connected vertically.
Reduce the concentric system after the first 0.8 metres to a diameter of 150/100 mm. The concentric system of 150/100
can be connected to an existing chimney.
The following requirements apply when connecting to an existing chimney:
- Only allowed when used in combination with the special DRU chimney kit.
- The internal dimensions should be at least 150 x 150 mm.
- The vertical length has a maximum of 12 metres.
- The total horizontal pipe length may have a maximum length (see table 7-3).
- The existing chimney has to be clean.
- The existing chimney has to be tight.
For adjusting the appliance, the same conditions/instructions apply as for the concentric system described above.
I nst allation manual
2 3
Summary of Contents for 0063CT3681
Page 12: ...Installation manual 12 800mm 800mm 38C 2601 85 C 50mm 7 2 ...
Page 14: ...Installation manual 14 ...
Page 19: ...Installation manual 19 ...
Page 21: ...Installation manual 21 ...
Page 22: ...Installation manual 22 ...
Page 25: ...Installation manual 25 ...
Page 31: ...Installation manual 31 B A 38P 0799 0 A A B 8 11 ...
Page 32: ...Installation manual 32 D C 38P 0800 0 8 12 ...
Page 33: ...Installation manual 33 F E 38P 0801 0 8 13 ...
Page 34: ...Installation manual 34 ...
Page 46: ...Installation manual 46 ...
Page 47: ...Installation manual 47 ...