7.3.2 Roof terminal (C31)
The roof terminal can end in a sloping and a flat roof.
The roof terminal can be supplied with an adhesive plate for a flat roof or with a universally adjustable tile for a sloping
roof.
When using a roof terminal (C31), the following applies:
The construction of the chosen system has to be allowed. The working method below indicates how the permissibility is
determined of a concentric system when using a roof terminal.
1
Count the number of 45° and 90° bends required (15° and 30° bends are also allowed; these are not counted).
1
Count the total number of whole metres of horizontal pipe length.
1
Count the total number of metres of vertical and/or sloping pipe length (roof terminal excluded).
1
Find the number of required bends and the total horizontal pipe length (see table 7-3, columns 1 and 2).
1
Find the required total vertical and/or sloping pipe length (see table 7-3, row 1).
1
A box with a letter means that the chosen concentric system is permitted.
1
Determine the adjustment of the appliance (see table 7-4).
1
Adjust the appliance correctly with, for instance, a restrictor slide and an air inlet guide (see section 8.2).
I nst allation manual
1 7
Summary of Contents for 0063CT3681
Page 12: ...Installation manual 12 800mm 800mm 38C 2601 85 C 50mm 7 2 ...
Page 14: ...Installation manual 14 ...
Page 19: ...Installation manual 19 ...
Page 21: ...Installation manual 21 ...
Page 22: ...Installation manual 22 ...
Page 25: ...Installation manual 25 ...
Page 31: ...Installation manual 31 B A 38P 0799 0 A A B 8 11 ...
Page 32: ...Installation manual 32 D C 38P 0800 0 8 12 ...
Page 33: ...Installation manual 33 F E 38P 0801 0 8 13 ...
Page 34: ...Installation manual 34 ...
Page 46: ...Installation manual 46 ...
Page 47: ...Installation manual 47 ...