4-2-15 Multifunction output terminals
}
Multifunction items can be output to the four terminals
shown left. (One of the terminals can be selected.)
1) No. 66
Term-11.Sel (terminal 11)
2) No. 67
Term-13.Sel (terminal 13)
3) No.68
Term-15.Sel (terminal 15)
4) No. 69
Term-16.Sel (terminal 16)
Register multifunction output items shown in Table 11 at each terminal. When a terminal is selected, the
functions shown in table 11 are displayed at the console for easy selection.
Table 11 Multifunction output items
No.
Function indication
Explanation
1
Arrive Ref.F
2
F=Detect1.F
3
F>= Detect1.F
4
F<= Detect1.F
5
F= Detect2.F
6
F>= Detect2.F
7
F<= Detect2.F
8
T>= Detect.T
Torque detection
The torque can be set in code No. 73 Detect.Torq (torque detection).
9
OL.Pre.Alarm
Overload pre-alarm
The specified value can be set in code No. 95 OL.Pre-Alarm
(overload pre-alarm setting)
10
Under Volt
Insufficient voltage
This is when the inverter is stopped due to insufficient voltage.
11
Reverse Now
Reverse operation in progress.
This is output when DIR/ REM at the console is set to REM.
12
Remote Now
Remote selection in progress.
This is output when reverse operation is performed.
13
Retrial Now
Retry in progress.
This is output when retry for restart is being performed.
14
P.Time Over
Termination of PGM operation.
This is output when the final stage of program operation is finished.
15
Alarm Code
Alarm code (see Table 12)
This is output when an error, fault, or failure has occured in the inverter.