DRI-STEEM Ultra-sorb Steam Dispersion Panel Installation, Operation, and Maintenance Manual • Page 25
Tr o u b l e s h o o t i n g g u i d e
Table 25-1:
Ultra-sorb troubleshooting guide
Problem
Possible cause
Action
Space humidity will not
rise to humidistat set
point
• Steam pressure too low
• Increase.
• Manual steam valve partially closed
• Open.
• Strainer screen partially clogged
• Clean.
• Boiler pressure too low
• Adjust control.
• Pressure reducing valve not accurately
controlling steam pressure
• Repair or replace.
• Boiler pressure swinging too widely
• Adjust controls.
• Incorrect piping
• Repipe. See Page 16.
• Undersized steam piping
• Replace.
• Undersized humidifier
• Replace valve with larger capacity valve.
• Replace with larger humidifier.
• Add additional humidifier.
• Automatic steam valve not fully opening
• Valve packing is adjusted too tightly, loosen and/or replace
packing.
• Adjust valve linkage.
• Recalibrate humidistat.
• Electric control system malfunctioning
• Change transformer.
• Incorrect control circuit voltage
• Replace component(s) to make all components compatible.
• Incorrect control signal
• Replace components.
• Improper wiring
• Rewire.
• Incorrect humidity sensor
• Replace sensor.
• Humidity controller out of calibration or
malfunctioning
• Repair or replace.
• Malfunctioning humidifier temperature switch
not allowing humidifier valve to open
• Replace or readjust.
• Pneumatic control system malfunctioning
• Repair or replace.
• Obstructed air line
• Remove obstruction.
• Malfunctioning pneumatic temperature switch
• Replace switch.
• Air leak in actuator
• Repair or replace diaphragm.
• Compressed air pressure is too low
• Adjust pressure.
Condensate in duct
• Foreign matter preventing valve from closing
• Clean or replace valve.
• Humidifier is mounted too close to internal
devices (dampers, turning vanes, etc.) in duct
• Move humidifier tubes to a point further upstream of internal
devices.
• Add more dispersion tubes for shorter non-wetting distance.
Consult DRI-STEEM to determine the total number of tubes
required.
• Non-insulated duct passing through unheated
area (duct surface temperature too low)
• Insulate ductwork.
US-IOM-0108.pdf 25
4/21/2010 11:34:59 AM