DRI-STEEM Ultra-sorb Steam Dispersion Panel Installation, Operation, and Maintenance Manual • Page 15
I n s t a l l a t i o n
Installation inside an air handling unit
See placement recommendation in Figure 11-1.
The metal support frame should be anchored to the air handler
casing. Recommended fasteners for mounting the Ultra-sorb to a
metal support frame are ¼ - 20 nuts and bolts or #12 self drilling
and tapping screws. Due to the possible forces exerted on this
application, DRI-STEEM recommends fastener spacing not to
exceed 6" (150 mm). On larger Ultra-sorb installations, vertical
channels may be required on both the inlet and outlet ends of the
humidifier to provide proper support. See Figure 15-2.
Air flow
Mounting channel (Typ)
Blank-off plate
Side blank-off
Steam supply header
Additional mounting support channels
required on larger Ultra-sorb units
Air handler casing
Supply header
Ultra-sorb
overall width
Steam
supply
AHU casing
AHU coil
Mounting
channel (Typ)
Floor drain
Condensate header
Blanked-off area
1" (25 mm) air gap
DC-1439
Figure 15-1:
Ultra-sorb installed inside an air handler
OM-199
Figure 15-2:
Vertical channels
Air
handler
overall
height
Air handler overall width
Ultra-sorb
overall
height
See Page 16 for trap dimensions.
US-IOM-0108.pdf 15