ULTRA-SORB MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Inspecting and servicing components
STRAINER
Inspect the strainer screen at least twice during the first year. If fouled, inspect it
more frequently.
STEAM TRAPS ON MAIN STEAM SUPPLY
At least twice a year verify that steam traps are functioning properly. A
blocked steam trap is cold. A "blowing" steam trap is hot and noisy, and the
discharge pipe from it is hot for 30 feet. A properly operating steam trap is hot
and makes noise at intervals, and the discharge pipe is progressively cooler
beginning at the trap.
VALVES
• Electric modulating:
Inspect annually to be sure that the valve operates freely and closes off
steam tightly and the stem packing is not leaking.
• Pneumatic:
Inspect annually to be sure the valve closes off steam tightly, the stem
packing is not leaking steam, and the diaphragm in the actuator is not
leaking air.
HIGH-EFFICIENCY TUBES
• If the insulating material gets dirty or smudged, gently clean it with a damp
cloth and a solution of soapy water or diluted non-toxic, biodegradable
cleaner/degreaser.
• Do not clean the insulating material with a pressure washer. The direct
spray could cause damage.
• If using a torch in the vicinity of the dispersion panel, keep the flame away
from the insulating material to avoid damage.
• PVDF is inherently resistant to UV light. Indirect, low-intensity UV-C light from
germicidal lamps will not cause the insulating material to degrade.
• Do not tighten mounting clamps or fasteners to any part of the dispersion
tube.
MAINTENANCE