ULTRA-SORB MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Field assembly
INSTALLATION
Note: These assembly instructions are for Ultra-sorb Model MP panels shipped
unassembled by request or as required. Panels with unit height more
than 93" (2360 mm) are shipped unassembled.
LAY OUT THE PANEL COMPONENTS
Place the panel components on a large, flat working surface.
ATTACH THE TOP FRAME ASSEMBLY
Span the flanges with the top frame assembly. Align the locating pins on the
flanges and top frame, and insert screws.
TIGHTEN THE FLANGE LOCKNUTS
Torque the eight flange locknuts to 16 ft-lb (22 N-m) at 100 rpm maximum
using a 7/16" deep-well socket.
INSTALL THE DISPERSION TUBES
Note: Do not remove the poly film from the dispersion tubes until after the
panel is installed.
Table 2-1:
Ultra-sorb Model MP components
Component
Qty .
Header assembly
1
Dispersion tubes
Varies
Top frame assembly
1
Side flanges
2
Screws
Varies
Flange locknuts
8
Header
assembly
Flange
locknut
Left side
flange
OM-7846
Top frame
assembly
Right side flange
Insulation
FIGURE 2-1: ULTRA-SORB MODEL MP COMPONENTS
Dispersion
tube
Locating pins