8
ULTRA-SORB MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Selecting the location
INSTALLATION
• Install the Ultra-sorb panel in a location where discharged water vapor will
be absorbed by the airstream.
• Place the Ultra-sorb panel where the air temperature is capable of
absorbing discharged steam without causing condensation at or after the
unit. This will normally be downstream from the heating coil where the air is
warmest.
• Do not place the Ultra-sorb panel in an outside air intake unless the air is
tempered with a preheat coil.
• Do not place the Ultra-sorb panel near the entrance of a high-efficiency
filter. The filter will remove visible moisture and become waterlogged. See
the Caution "Installing the Ultra-sorb panel upstream from filter media" on
• Do not place the Ultra-sorb panel where discharged visible mist will
impinge directly on a metal surface.
DETERMINE HUMIDIFIER PLACEMENT
Dispersed steam must be absorbed into the airflow before it comes in
contact with duct elbows, fans, vanes, filters, or any object that can cause
condensation and dripping.