1
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
Important:
This equipment is for use with the
following appliance categories.
Contact your distributor before
converting to another group or supply
pressure.
Table 1-1:
Appliance categories
I
2H
G20 at 20 mbar
I
2E
G20 at 20/25 mbar
I
2E+
G20/G25 at 20/25 mbar
I
2L
G25 at 25 mbar
I
3+(28-30/37)
G30 Butane at 28-30 mbar and
G31 Propane at 37 mbar
I
3B/P(30)
G30 Butane and
G31 Propane at 30 mbar
I
3B/P(37)
G30 Butane and
G31 Propane at 37 mbar
I
3B/P(50)
G30 Butane and
G31 Propane at 50 mbar
I
3P(30)
G31 Propane at 30 mbar
I
3P(37)
G31 Propane at 37 mbar
I
3P(50)
G31 Propane at 50 mbar
Electrical warning label
Location:
Front door and electrical
access
door
Defi nition:
Electrical shock hazard
An input derate exists when operating
GTS humidifi ers at a high altitude.
Table 1-2:
Input derate for high altitude
Altitude (meters)
Input derate %
0 – 610
0
611 – 765
2
766 – 915
4
916 – 1065
6
1066 – 1220
8
1221 – 1370
10
1371 – 1525
12
1526 – 1675
14
1676 – 1830
16
1831 – 1980
18
1981 – 2135
20
2136 – 2285
22
2286 – 2440
24
2441 – 2590
26
2591 – 2743
28
2744 – 2895
30
2896 – 3048
32
3049 – 3200
34
3201 – 3352
36
3353 – 3505
38
3506 – 3657
40
This equipment has been tested by
Intertek to the Low Voltage, Gas
Appliance, and EMC directives and
has been certifi ed by Certigaz for use
in all EU countries.
GTS humidifi ers bearing the CE
mark are authorized for use in the
European countries listed below.
Table 1-3:
Authorized countries of destination
Austria (AT)
Latvia (LV)
Belgium (BE)
Lithuania (LT)
Bulgaria (BG)
Luxembourg (LU)
Cyprus (CY)
Malta (MT)
Czech Republic (CZ)
Netherlands (NL)
Denmark (DK)
Norway (NO)
Estonia (EE)
Poland (PL)
Finland (FI)
Portugal (PT)
France (FR)
Romania (RO)
Germany (DE)
Slovakia (SK)
Greece (GR)
Slovenia (SI)
Hungary (HU)
Spain (ES)
Iceland (IS)
Sweden (SE)
Ireland (IE)
Switzerland (CH)
Italy (IT)
United Kingdom (GB)
Table 1-4:
Gas specifications for GTS models
GTS
model
Volumetric fl ow rate by gas category
Average
fl ue
temperature
at 100%
demand
Minimum
draught
requirement
Mass fl ow
rate of
combustion
products
2H-G20-20 mbar
2E-G20-20 mbar
2Es-G20-20 mbar
2L-G25-25 mbar
2LL-G25-20 mbar
2Ei-G25-25 mbar
2E+G20/G25-20/25 mbar
2ER-G20/G25-20/25 mbar
3B-G30-30 mbar
3B-G30-50 mbar
3P-G31-30 mbar
3P-G31-37 mbar
3P-G31-50 mbar
100
2.31 m
3
/h
2.82 m
3
/h
2.31-2.82 m
3
/h
1.31 m
3
/h
1.49 m
3
/h
200 °C
– 0.025 mbar
6.9 g/s
200
4.62 m
3
/h
5.64 m
3
/h
4.62-5.64 m
3
/h
2.62 m
3
/h
2.98 m
3
/h
220 °C
– 0.025 mbar
13.8 g/s
300
6.93 m
3
/h
8.46 m
3
/h
6.92-8.46 m
3
/h
3.93 m
3
/h
4.47 m
3
/h
190 °C
– 0.025 mbar
20.7 g/s
400
9.24 m
3
/h
11.28 m
3
/h
9.24-11.28 m
3
/h
5.24 m
3
/h
5.96 m
3
/h
220 °C
– 0.025 mbar
27.6 g/s
500
11.55 m
3
/h
14.10 m
3
/h
11.55-14.10 m
3
/h
6.55 m
3
/h
7.45 m
3
/h
220 °C
– 0.025 mbar
34.5 g/s
600
13.86 m
3
/h
16.92 m
3
/h
13.85-16.92 m
3
/h
7.86 m
3
/h
8.94 m
3
/h
220 °C
– 0.025 mbar
41.4 g/s
700
16.17 m
3
/h
19.74 m
3
/h
16.17-19.74 m
3
/h
9.17 m
3
/h
10.43 m
3
/h
220 °C
– 0.025 mbar
48.3 g/s
800
18.48 m
3
/h
22.56 m
3
/h
18.47-22.56 m
3
/h
10.48 m
3
/h
11.92 m
3
/h
220 °C
– 0.025 mbar
55.2 g/s
Before you begin