DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL

Supply water piping 

TAP/SOFTENED WATER 

The primary component of the supply water assembly is a solenoid valve, 
which may cause noise during fi ll cycles.

During a fi ll cycle, cold supply water drops the internal tank temperature and 
may collapse the boil, which can cause a low rolling sound. To minimize this, 
use hot supply water.

In cases where water hammer occurs when the fi ll solenoid closes, a shock 
arrester is recommended. Reducing the supply water pressure (minimum 
172 kPa with fi ll valve open) or using fl exible tubing (rated for 100 °C 
minimum continuous operating temperature) may diminish the noise.  

The minimum water conductivity for the GTS tap/softened water model 
is 30 µS/cm.

RO/DI WATER OPTION 

The water level in GTS humidifi ers with the RO/DI water option is controlled 
with a fl oat valve. For models with the end-of-season drain option, a solenoid 
valve is installed prior to the fl oat valve. 

When using nonmetallic tubing, DriSteem recommends the installer place a 
50-mm water seal/loop in the supply water line to isolate steam during RO/DI 
water system maintenance. 

DriSteem highly recommends installing a strainer in the supply water line 
to prevent clogging of the solenoid valve or fl oat valve orifi ce. The strainer 
prevents particulate from collecting at the solenoid valve seat.

To minimize RO/DI water waste, disconnect factory piping to the water 
tempering device and pipe directly to a tap water source.

  

WARNING

 

Fire hazard if using tap/softened supply water with RO/DI water option:

If a GTS humidifier with the RO/DI water option is supplied with 
tap/softened fill water, the float valve assembly will become clogged, 
and particulate will accumulate on the low water cutoff switch (float 
switch). This will cause failure of a critical safety circuit and the potential 
for a dry tank fire, which can cause severe property damage, severe 
personal injury, or death.

SUPPLY WATER FLOW RATES

The rate of supply water fl ow into the GTS humidifi er tank is determined by the 
supply water pressure and the inlet valve. See Table 6-2.

mc_071912_1545

SUPPLY WATER GUIDELINES 

Supply water quality is an important 
component of humidifier reliability and 
maintenance.

Examples: 
•  Corrosive water can decrease the 

service life of the humidifier.

•  Excessive water hardness can 

increase the humidifier maintenance 
requirements. 

To maximize humidifier service life 
and minimize humidifier maintenance, 
DriSteem has established guidelines for 
supply water See Table 6-1.

Table 6-1:
DriSteem supply water guidelines

Chlorides*

RO or DI water

Softened water

Tap water

*  Damage caused by 

chloride corrosion is 
not covered by your 
DriSteem warranty.

< 5 ppm

< 25 ppm

< 50 ppm

Total hardness

Tap water

< 500 ppm

pH

RO, DI, or softened 
water

Tap water

7 to 8

6.5 to 8.5

Silica

< 15 ppm

You may wish to take action to mitigate 
potential negative effects to your 
humidifi er. Supply water outside of these 
guidelines may void your DriSteem 
warranty. Please contact your DriSteem 
distributor if you need advice.

Table 6-2:
Supply water flow rates (liters per minute)

Supply 

water

pressure

Solenoid valve fl ow rates

(tap/softened water)

Float valve fl ow rates (RO/DI water)

Models 100 – 400

Models 500 – 800

200 kPa

7.2

6.7

17.0

350 kPa

9.0

8.8

22.5

450 kPa

10.2

9.9

25.4

550 kPa

11.1

10.8

27.6

Summary of Contents for GTS-100

Page 1: ...b b b l l l l l l l he he he he he e he e e ere re re re re re re re r Following installation of this steam generating humidifier the installer shall instruct the user in the operation of the steam g...

Page 2: ...ly water piping requirements for all water types 5 Supply water piping Tap softened water 6 RO DI water option 6 Supply water flow rates 6 Supply water guidelines 6 Drain piping 7 Gas piping 8 Combust...

Page 3: ...the European countries listed below Table 1 3 Authorized countries of destination Austria AT Latvia LV Belgium BE Lithuania LT Bulgaria BG Luxembourg LU Cyprus CY Malta MT Czech Republic CZ Netherland...

Page 4: ...ers off and tries to fill the tank If unable to fill the tank within a defined time period an Excessive refill time alarm appears in the Vapor logic Alarm Log The burners remain off until this alarm i...

Page 5: ...off switch if DI RO water option Water level probe Float operated low water cutoff switch if DI RO water option Thermal trip Temperature sensor Tap softened water GTS humidifier shown Steam hose or tu...

Page 6: ...f the structure When such locations cannot be avoided install a suitable drain pan adequately drained under the humidifier The pan must not restrict combustion airflow If located in an insulated space...

Page 7: ...er system while servicing To minimize electrolytic corrosion install insulating unions to make connections between copper and other dissimilar metal fittings such as galvanized steel Humidifier tank m...

Page 8: ...r option If a GTS humidifier with the RO DI water option is supplied with tap softened fill water the float valve assembly will become clogged and particulate will accumulate on the low water cutoff s...

Page 9: ...s adversely affecting their life and performance An open drain with a 25 mm air gap between the drain piping and the drain is required Locate the air gap only in spaces with adequate temperature and a...

Page 10: ...ches when connecting piping to humidifier or controls Provide a drip leg before each humidifier and in the line where low spots cannot be avoided Take off to humidifier should come from top or side of...

Page 11: ...nnection immediately upstream of the gas supply connection to the appliance Use this tap to check pressure with all burners running Leak testing After installation check field piping and humidifier ga...

Page 12: ...xygen for proper combustion openings must be provided to allow outside air to enter the space where the humidifier is located Enclosed spaces such as equipment rooms must be vented for combustion air...

Page 13: ...piping All GTS models have a single point connection to the blower inside the front door See Figure 11 3 When running PVC or CPVC piping for sealed combustion the maximum allowable distance to the out...

Page 14: ...ed according to the provisions of the governing codes Venting Vent connector serving this appliance shall not be connected into any portion of mechanical draft systems operating under positive pressur...

Page 15: ...L VENTING REQUIREMENTS Contact your DriSteem distributor for all horizontal venting parts Ensure that distances from vent terminal to adjacent public walkways buildings and openable windows and buildi...

Page 16: ...e GTS wiring diagrams Control wiring Verify that all control wiring has been completed as specified and required for correct and safe operation of the GTS humidifier Tank Verify that the humidifier ta...

Page 17: ...l down as described here NOTE Insulated and uninsulated tanks will have hot surfaces Verify that there is no call for humidity and that the aquastat set point adjusted using the keypad display Setup s...

Page 18: ...minerals have hardened in the water seal Clean the low water cutout probe Remove the electrical access panel and inspect the probe rod for mineral accumulation The probe rod is located on the top of t...

Page 19: ...ward and physically sound without holes or excessive corrosion Ensure that physical support of the humidifier is sound without sagging cracks or gaps between floor stand or tank flanges Ensure that th...

Page 20: ...ns BURNER MAINTENANCE FREQUENCY Under normal use conditions the burner s should not need cleaning for a minimum of five years However depending on the operating environment the burner s may require pe...

Page 21: ...less than 40 ppm low single digits is the norm CO2 from 8 to 10 preferably 9 O2 between 4 and 7 Flue Temperature less than 204 C plus room temperature Burner efficiency greater than 80 Orange color f...

Page 22: ...act negligence strict liability in tort or any other legal theory even if DriSteem has notice of the possibility of such damages By purchasing DriSteem s products the purchaser agrees to the terms and...