DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL

•  The GTS humidifi er is a Fan Assisted Category I 

(natural draft) Appliance. It is a Class B23 appliance, 
without a draught diverter, with a combustion 
air blower upstream of the heat exchanger. A 
GTS humidifi er with the sealed combustion option is 
a Class C53 appliance. Installations where the vent 
terminates in a side wall of the building, or where the 
overall horizontal run exceeds the overall vertical run, 
require a power venter.

• Maximum 

fl ue temperature under normal operating 

conditions is 205 °C plus ambient.

•  Maximum abnormal-operation fl ue temperature is 

348 °C plus ambient.

•  Flue draft negative pressure greater than 50 Pa may 

cause unacceptable post ignition.

•  Vent piping must be approved for a Category I 

appliance. Do not use more than one type of venting 
per application.

•  Vent terminal must be at least 1 m above  any forced 

air inlet located within 3 m.

•  Do not use vent equipment from more than one 

manufacturer.

•  When connecting the humidifi er to a gas vent or 

chimney, installation must conform to:
–  Local and national directives and regulations for 

the installation of gas-fi red equipment

–  Governing and building codes
–  Vent manufacturer’s instructions

•  When applying the codes, see also the venting 

manufacturer's instructions, the service gas supplier's 
regulations, and the specifi c instructions provided in 
this manual. 

•  Inspect for proper and tight construction. Remove any 

restrictions or obstructions. An existing chimney may 
require cleaning.

•  Do not connect this humidifi er to a chimney fl ue 

servicing a separate appliance designed to burn solid 
fuel.

•  Never connect this humidifi er to a chimney serving a 

fi replace, unless the fi replace opening is permanently 
sealed off.

•  Code prohibits venting into an unlined masonry 

or concrete chimney. If the humidifi er is connected 
to a lined, masonry chimney, the chimney must be 
sized and installed according to the provisions of the 
governing codes.

Venting 

•  Vent connector serving this appliance shall not be 

connected into any portion of mechanical draft 
systems operating under positive pressure.

•  Add insulation to any roof or wall penetration vent 

connector that is exposed to ambient temperatures of 
0 °C or less, especially any application using single-
wall vent pipe as a connector.

•  Do not insulate vent pipe exposed to outdoor weather 

conditions (e.g., above roof lines).

•  Install vent piping as straight as possible, with a 

minimum number of turns or elbows.

•  Maintain a minimum upward slope of 2% on all 

horizontal runs. 

•  Rigidly support the vent pipe every 1.5 m or less with 

hangers or straps to ensure there is no movement after 
installation. The humidifi er vent box should not support 
the weight of the vent piping.

•  No portion of the vent system should extend into, or 

pass through, any circulation air duct or plenum.

•  Install and fi re-stop all vent pipe passing through 

fl oors, ceilings, and walls with the proper clearances 
from combustible material according to local and 
national directives and regulations for the installation 
of gas-fi red equipment.

•  In replacement installation where an existing vent 

system may be used, inspect the vent system for 
condition, size, type of vent material, and height to 
meet the requirements in these instructions. 

CAUTION

 

Flue condensate removal

Install a drip leg or fl ue box condensate drain for start-
up fl ue condensate removal. Failure to follow these 
instructions could cause water to accumulate in the 
fl ue box.

OUTDOOR ENCLOSURE VENTING 

The vertical section of fl ue must be at least 1.5 meters or 
meet all governing codes, whichever is longer. DriSteem 
recommends a drip tee directly after the factory-supplied vent 
connection. DriSteem recommends a high-wind vent cap on 
all GTS humidifi ers. See Figure 4-2.

GENERAL VENTING GUIDELINES 

  

WARNING

 

Installation requirements:

The humidifi er must be installed by a qualifi ed technician and meet the requirements of all governing codes. 
Failure to follow these instructions could cause severe bodily injury or death.

Summary of Contents for GTS-100

Page 1: ...b b b l l l l l l l he he he he he e he e e ere re re re re re re re r Following installation of this steam generating humidifier the installer shall instruct the user in the operation of the steam g...

Page 2: ...ly water piping requirements for all water types 5 Supply water piping Tap softened water 6 RO DI water option 6 Supply water flow rates 6 Supply water guidelines 6 Drain piping 7 Gas piping 8 Combust...

Page 3: ...the European countries listed below Table 1 3 Authorized countries of destination Austria AT Latvia LV Belgium BE Lithuania LT Bulgaria BG Luxembourg LU Cyprus CY Malta MT Czech Republic CZ Netherland...

Page 4: ...ers off and tries to fill the tank If unable to fill the tank within a defined time period an Excessive refill time alarm appears in the Vapor logic Alarm Log The burners remain off until this alarm i...

Page 5: ...off switch if DI RO water option Water level probe Float operated low water cutoff switch if DI RO water option Thermal trip Temperature sensor Tap softened water GTS humidifier shown Steam hose or tu...

Page 6: ...f the structure When such locations cannot be avoided install a suitable drain pan adequately drained under the humidifier The pan must not restrict combustion airflow If located in an insulated space...

Page 7: ...er system while servicing To minimize electrolytic corrosion install insulating unions to make connections between copper and other dissimilar metal fittings such as galvanized steel Humidifier tank m...

Page 8: ...r option If a GTS humidifier with the RO DI water option is supplied with tap softened fill water the float valve assembly will become clogged and particulate will accumulate on the low water cutoff s...

Page 9: ...s adversely affecting their life and performance An open drain with a 25 mm air gap between the drain piping and the drain is required Locate the air gap only in spaces with adequate temperature and a...

Page 10: ...ches when connecting piping to humidifier or controls Provide a drip leg before each humidifier and in the line where low spots cannot be avoided Take off to humidifier should come from top or side of...

Page 11: ...nnection immediately upstream of the gas supply connection to the appliance Use this tap to check pressure with all burners running Leak testing After installation check field piping and humidifier ga...

Page 12: ...xygen for proper combustion openings must be provided to allow outside air to enter the space where the humidifier is located Enclosed spaces such as equipment rooms must be vented for combustion air...

Page 13: ...piping All GTS models have a single point connection to the blower inside the front door See Figure 11 3 When running PVC or CPVC piping for sealed combustion the maximum allowable distance to the out...

Page 14: ...ed according to the provisions of the governing codes Venting Vent connector serving this appliance shall not be connected into any portion of mechanical draft systems operating under positive pressur...

Page 15: ...L VENTING REQUIREMENTS Contact your DriSteem distributor for all horizontal venting parts Ensure that distances from vent terminal to adjacent public walkways buildings and openable windows and buildi...

Page 16: ...e GTS wiring diagrams Control wiring Verify that all control wiring has been completed as specified and required for correct and safe operation of the GTS humidifier Tank Verify that the humidifier ta...

Page 17: ...l down as described here NOTE Insulated and uninsulated tanks will have hot surfaces Verify that there is no call for humidity and that the aquastat set point adjusted using the keypad display Setup s...

Page 18: ...minerals have hardened in the water seal Clean the low water cutout probe Remove the electrical access panel and inspect the probe rod for mineral accumulation The probe rod is located on the top of t...

Page 19: ...ward and physically sound without holes or excessive corrosion Ensure that physical support of the humidifier is sound without sagging cracks or gaps between floor stand or tank flanges Ensure that th...

Page 20: ...ns BURNER MAINTENANCE FREQUENCY Under normal use conditions the burner s should not need cleaning for a minimum of five years However depending on the operating environment the burner s may require pe...

Page 21: ...less than 40 ppm low single digits is the norm CO2 from 8 to 10 preferably 9 O2 between 4 and 7 Flue Temperature less than 204 C plus room temperature Burner efficiency greater than 80 Orange color f...

Page 22: ...act negligence strict liability in tort or any other legal theory even if DriSteem has notice of the possibility of such damages By purchasing DriSteem s products the purchaser agrees to the terms and...