aerosmart - Operation, Maintenance and Commissioning
Page 17
Setting the Default Set-Point Room Temperature
Stnd. Sollwert: 21.5°C
Standard set-point temperature
Akt. Sollwert: 20.3°C
Set-point temperature
Nachtabsenkung: 0.0°C
Reduced set-point temperature
Von/Bis: 22:00/06:00
From/ To:
Stnd. Sollwert
When using the analogue room operating panel, the user can turn the dial to adjust the room
set-point temperature by +/- 3°C. The middle dial setting is programmed. The default set-
point can lie between 18 and 24°C.
Note:
This option is not available when using the digital room operating panel as the de-
sired temperature is directly programmed on the room operating panel.
Akt. Sollwert
Current set-point: air temperature measured by the room gauge. This value cannot be ad-
justed.
Nachtabsenkung der Raumsolltemperatur
This can be used to reduce the room set-point temperature for a freely defi nable period of
the day
(Default set-point) by up to 5°C.
Von/Bis: 22:00/6:00
Enter the time period for the reduction of the room set-point
temperature.
Room Heating Cut-Off
This function can be used to briefl y disable the room heating if the temperature in the
domestic water storage tank falls below a specifi c level. During the cut-off, the heat pump
is only used to heat the domestic water. Two menu pages are available to set the room
heating cut-off:
<TECHNIKEREBENE>
Technician Level
Fühlerwahl für
Temperature gauge for
Sperre Raumheizung
Room heating cut-off
BOILERTEMP.MITTE
Middle boiler temp.
This parameter determines the temperature gauge used for the room heating cut-off. If there
is a high level of warm water usage, this parameter can be set to '
BOILERTEMP.UNTEN
'.
BOILERTEMP.UNTEN
Lower boiler temperature
BOILERTEMP.MITTE
Middle boiler temperature