aerosmart - Operation, Maintenance and Commissioning
Page 18
<TECHNIKEREBENE>
Technician Level
Sperre Raumheizung
Room Heating cut-off
Soll: 35°C
Set
Diff: 07.0°C
Difference
Soll
By increasing the set-point, the warm water comfort can be increased.
Diff
The 'Difference' value describes the hysteresis, the exceeding of which deactivates the room
heating cut-off.
Setting the Nominal Air Quantities
<TECHNIKEREBENE>
Technician Level
Nennluftmenge:
Nominal air quantity
### m3/h
(Lüfterstufe 2)
(fan level 2)
This parameter is used to program the system's nominal air quantity. Please refer to the
house technology planning for the value to be set.
Note:
It is only necessary to enter the nominal air quantity for fan level 2. The air quanti-
ties for levels 1 and 3 are automatically defi ned with -30% (level 1) and +30% (level 3).
Timeframe for Fan Control
There are two available menu pages for the temporal programming of the fans. The de-
fault level is fan level 2, which does not have to be programmed. This level always applies
when no timeframe is enabled.
Zeitprogramm 1
Time program 1
Lüfterstufe: 1
Fan level
Beginn: 00:00
Start
Ende: 00:00
End
For example, program a timeframe for fan level 1 for the time of day at which the house is
usually empty.
Zeitprogramm 2
Time program 2
Lüfterstufe: 3
Fan level
Beginn: 00:00
Start
Ende: 00:00
End
You can also program a timeframe for fan level 3, for example, for fi xed cooking times.
Note:
You can set two time programs for fan level 1 or two time programs for
fan level 3.