Figure 36: Test Pulse Outputs on the Advanced screen
9.2
Wiring Instructions for Hazardous Locations
To maintain compliance with CSA certification, use a suitable Intrinsic Safety barrier for a Class 1,
Division 1 hazardous area for groups A, B, C, and D.
Do not exceed the following input values for the barrier device:
•
Vi = 8.2V
•
li = 10 ma
The OUTPUT and power handling capability of a barrier should not exceed:
•
Vout = 30V
•
lout = 50 ma
For hazardous areas, use a recommended barrier such as Turck Brand IM1-12EX-T Single Channel or
IM1-22 EX-R Dual Channel Barrier or an equivalent.
For wiring products in hazardous locations, refer to the
Dresser™ Series D Meter Installation, Operation,
and Maintenance Manual
.