MCS – MicroMag Error / Alarm Manual
Version: 02/21/2020
This alarm will trip if the discharge pressure rises
above the value of Setpoint #70. If the compressor
has high discharge pressure, it locks out the
compressor and the HI DIS PSI alarm will display.
Note: Supervisor password (2112) is
required to reset lockouts
MicroMag Alarms
Possible Causes
Solutions
Sensor fault on
discharge pressure
See Appendix B to troubleshoot
Condenser panels
removed
Replace the panels on the chiller
Condenser dirty or
damaged
(Air-cooled)
Clean or replace condenser coils
(shown to the right)
Condenser blocked
(Air-cooled)
Poor installation location (overhang, other equipment installed too
close, wall, fence or other object is within 3’ of the chiller blocking
airflow
Fans not running
(Air-cooled)
Verify fuses are not blown
(left picture)
Carefully, with ONLY an
insulated screwdriver, bump
the condenser contactor at
the circled spot to see if fans
turn on (right picture)
Restriction in cooling
water
(Water-cooled)
Confirm that all valves are opened
Adjust regulator (shown to the right)
Refrigerant Overcharge
Contact Drake
High Discharge
Pressure
3
.