MCS – MicroMag Error / Alarm Manual
Version: 02/21/2020
This alarm will trip if the discharge pressure
drops below the value of Setpoint #69. If the
compressor has low discharge pressure, it will
lockout and display the LO DIS PSI alarm.
Note: Supervisor password (2112) is
required to reset lockouts
MicroMag Alarms
Possible Causes
Solutions
Sensor fault on
discharge pressure
See Appendix B to troubleshoot
Condenser fans not
cycling properly
Check Setpoint #17 to ensure enough head pressure is being built
Flooded head pressure
controls (Receivers
only)
Adjust the ORI valve (shown to the right) for a
higher receiver pressure setting
Refrigerant charge is
low
Check for refrigerant leak
Contact Drake to determine the charge
Low Discharge
Pressure