20
Technical data
en
7.2
Wiring options
For more information on relay connection and wiring options, please
refer to the Technical Manual.
7.2.1
Dräger Flame 2100/2350
The following table describes the function of each terminal for all the
wiring options.
Terminal
no.
Option 1
(default)
Option 2 Option 3 Option 4 Option 5
1
+24 VDC +24 VDC +24 VDC +24 VDC +24 VDC
2
0 VDC
0 VDC
0 VDC
0 VDC
0 VDC
3
Manual
BIT
Manual
BIT
Manual
BIT
Manual
BIT
Manual
BIT
4
Fault
Relay C
1)
Fault
Relay C
Fault
Relay C
Fault
Relay C
Fault
Relay C
5
Fault Re-
lay N.C.
Fault Re-
lay N.C.
Fault Re-
lay N.O.
Fault Re-
lay N.C.
Fault Re-
lay N.O.
6
Alarm Re-
lay N.O.
2)
Alarm Re-
lay N.O.
2)
Alarm Re-
lay N.O.
2)
Alarm Re-
lay N.O.
2)
Alarm Re-
lay N.O.
2)
7
Alarm Re-
lay C
Alarm Re-
lay C
Alarm Re-
lay C
Alarm Re-
lay C
Alarm Re-
lay C
8
0-20 mA
In
Alarm Re-
lay N.C.
Alarm Re-
lay N.C.
Auxili-
ary
3)
N.O.
Auxili-
ary
3)
N.O.
9
0-20 mA
Out
4)
0-20 mA
Out
4)
0-20 mA
Out
4)
Auxiliary
C
Auxiliary
C
10
RS-485+
(1)
5)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
11
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
12
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
1)
C = Common (dry contact); N.C. = Normally Closed; N.O. = Normally Open,
GND = Ground; SPST = Single Pole Single Throw
2)
In options 1, 4, and 5, the alarm relay is N.O. (terminals 6 and 7).
In options 2 and 3, the alarm relay is N.O. (terminals 6 and 7) or N.C. (ter-
minals 7 and 8).
3)
The auxiliary output is a N.O. (SPST) relay. The auxiliary relay may act in
parallel with the alarm relay to activate another external device or it may
provide a warning signal, depending on the function configuration.
4)
Available with the HART protocol
0-20 mA is ‘sink’ in option 1 and ‘source’ in option 2 and 3. The maximum
permitted load is 600
Ω.
In wiring option 1, link terminals 1 and 8 to change the mA output to ‘source’.
5)
For MODBUS protocol, (1) indicating the flame detector address
Terminal
no.
Option 1
(default)
Option 2 Option 3 Option 4 Option 5
Summary of Contents for Flame 2100
Page 2: ......
Page 120: ...120 ru 1 1 1 5 135 Dr ger Dr ger Dr ger Dr ger Dr ger 1 2 2 2 1 A 1 2 3 4 5 6 7...
Page 126: ...126 ru 3 3 1 NFPA 72 Ex 3 NFPA 72 30 12 45 18...
Page 127: ...127 ru Dr ger Flame 2350 2370 45 3 2 3 344...
Page 130: ...130 ru A 2 5 15 10 0 3 5 10 15 20 30 0 20 247 BIT 1 BIT BIT BIT 1 BIT 3 BIT 2 YES...
Page 134: ...134 ru 4 0 20 0 Dr ger 4 0 20 0 24 Dr ger 4 0 20 2 BIT Dr ger 0 20 20 Dr ger...
Page 135: ...135 ru 5 5 1 Dr ger 5 2 1 2 3 5 3 1 2 3 3 9 131 3 Dr ger 6 5 2 135 5 3 135 6 1 1 Dr ger Dr ger...
Page 144: ......
Page 145: ......