17
Troubleshooting
en
3.4
During use
3.4.1
General notes
After powering-up, the flame detector requires almost no attention to
function properly, but the following should be noted:
Do not expose the flame detector to radiation of any kind unless
required for testing purposes.
Do not expose the Dräger Flame 2100 to a UV radiation source
(for example: welding, sparks, electronic arc), as this will result in
a false alarm.
Do not open the detector housing while power is applied - there is
a risk of ignition of hazardous atmospheres.
Do not open the electronic compartment. This part should be kept
closed always and only opened in the factory. Opening the
electronic component side invalidates the warranty.
Only access the wiring compartment to wire or remove the
detector or access RS485 terminals for maintenance.
3.4.2
Manual reset
Note
: Most detectors are used in the non-latching alarm mode. Only
perform a reset when the latching alarm option has been programmed.
Disconnect power (terminal number 1 or terminal number 2).
or
Initiate a manual BIT (Dräger Flame 2100/2350 only).
4
Troubleshooting
Problem
Cause
Corrective action
Status LED off
Fault relay at N.O.
0-20 mA output at
0 mA
Flame detector not
energized
Check that the
correct power is
applied to the
flame detector.
Check power
polarity.
Check wiring in
the flame
detector.
Send the flame
detector to Dräger
for repairs.
Status LED flashes
yellow at 4 Hz
Fault relay at N.O.
0-20 mA output at
0 mA
Detector fault
Low voltage
Faulty flame
detector
Check the voltage
at the flame
detector; verify at
least 24 V at the
detector terminal.
Send the flame
detector to Dräger
for repairs.
Status LED flashes
yellow at 4 Hz
Fault relay at N.O.
0-20 mA output at
2 mA
BIT fault
Faulty flame
detector
Clean detector
window.
Repower the
flame detector.
Send the flame
detector to Dräger
for repairs.
Status LED lights
constantly red
If no fire exists, the
alarm is latched.
Reset the flame
detector.
Summary of Contents for Flame 2100
Page 2: ......
Page 120: ...120 ru 1 1 1 5 135 Dr ger Dr ger Dr ger Dr ger Dr ger 1 2 2 2 1 A 1 2 3 4 5 6 7...
Page 126: ...126 ru 3 3 1 NFPA 72 Ex 3 NFPA 72 30 12 45 18...
Page 127: ...127 ru Dr ger Flame 2350 2370 45 3 2 3 344...
Page 130: ...130 ru A 2 5 15 10 0 3 5 10 15 20 30 0 20 247 BIT 1 BIT BIT BIT 1 BIT 3 BIT 2 YES...
Page 134: ...134 ru 4 0 20 0 Dr ger 4 0 20 0 24 Dr ger 4 0 20 2 BIT Dr ger 0 20 20 Dr ger...
Page 135: ...135 ru 5 5 1 Dr ger 5 2 1 2 3 5 3 1 2 3 3 9 131 3 Dr ger 6 5 2 135 5 3 135 6 1 1 Dr ger Dr ger...
Page 144: ......
Page 145: ......