13
Dräger Flame 3000
6.
Connect the cabling to the terminals in one of the following configurations:
4 – 20 mA output.
Relay output.
24 Vdc
0 Vdc
To fire panel
To fire panel
End of
line
resistor
Alarm
3878
7.
Apply an even coating of non-setting waterproof grease to the flame path on both the enclosure rear cover and body.
8. Fully screw the rear enclosure cover to the enclosure body. Ensure that the O-ring is beneath the cover and that the set screw will not interfere with
or be screwed into the threads of the flame path or the O-ring. Secure the rear enclosure cover in place with the set screw.
WARNING
Do not use the Dräger Flame 3000 if the rear enclosure cover cannot be screwed onto the enclosure body by five or more full turns.
The detector has insufficient explosion protection (the flame path is too short) and using it in an explosive atmosphere may lead to an
explosion. Return the detector to Dräger for investigation/repair.
!
24 Vdc
0 Vdc
4-20 mA source
Use
Summary of Contents for 420 94 60