Before Installing

Please  thoroughly  read  the  system  wiring  and  installation 
manuals,  and  manual  I56-407, 

Guide  for  Proper  Use  of 

System Smoke Detectors, 

which provides detailed informa-

tion  on  detector  spacing,  placement,  zoning,  and  special 
applications.  Copies  of  these  manuals  are  available  at  no 
charge from System Sensor.  

 

 

 

 

 

 

 

 

 

 

NOTICE:

 This manual should be left with the owner/user 

of this equipment.

  

IMPORTANT:

  The  detector  used  with  these  bases  must 

be  tested  and  maintained  regularly  following  NFPA  72 
requirements.  The  detectors  should  be  cleaned  at  least 
once a year.

  

Mounting

The detector base mounts directly to 3

1⁄2

- and 4-inch octa-

gon  and  4-inch  square  boxes,  with  or  without  a  plaster 
ring.

To mount, remove the decorative ring by rotating it in either 
direction to unhook the snaps. Then, separate the ring from 
the base. Install the base on the box, using the screws sup-
plied with the junction box and the appropriate slots in the 
base. Replace the decorative ring on the base and rotate it in 
either direction until the ring snaps in place (see Figure 1).

Specifications

Base Diameter: 

6.1 inches (155 mm)

Base Height                   

1.2 inches (31 mm)

Mounting: 

4-inch square box with or without plaster ring, Min Depth - 1.5 inches (13 mm)

 

4-inch octagon box, Min. depth - 1.5 inches (13 mm)

 

3

1/2

-inch octagon box, Min. depth - 1.5 inches (13 mm)

Operating Temperature Range: 

0° to 49°C (32° to 120°F)

Operating Humidity Range: 

10% to 93% Relative Humidity, noncondensing

Electrical Ratings

Operating Voltage: 

15 to 32 VDC

Currents: 
 

Detector– 

230µA@24VDC (without communication)

 

 

285µA@24VDC (one communication every 5 seconds with LED enabled)

 

Air Intake– 

6mA standby

 

 

60mA when checking for smoke (5 seconds on, 30 seconds off)

 

 

80mA when checking for proper airflow (15 seconds on, every 4 hours)

Installation Guidelines

All wiring must be installed in compliance with all appli-
cable local codes and any special requirements of the local 
authority having jurisdiction, using the proper wire sizes. 
The conductors used to connect smoke detectors to control 
panels  and  accessory  devices  should  be  color-coded  to 
reduce  the  likelihood  of  wiring  errors.  Improper  connec-
tions can prevent a system from responding properly in the 
event of a fire.

For signal wiring (the wiring between interconnected detec-
tors), it is recommended that the wire be no smaller than 
18  gauge  (1.0  square  mm).  However,  wire  sizes  up  to  12 
gauge  (3.3  square  mm)  can  be  used  with  the  base.  The 
use of twisted pair wiring or shielded cable for the power 
(+ and –) loop is recommended to minimize the effects of 
electrical interference.

If shielded cable is used, the shield connection to and from 
the detector must be continuous by using wire nuts, crimp-
ing, or soldering, as appropriate, for a reliable connection.

Alarm system control panels have specifications for allow-
able  loop  resistance.  Consult  the  control  panel  specifica-
tions  for  the  total  loop  resistance  allowed    before  wiring 
the detector loops.

B501B-FTX Detector Base

For use with the Filtrex™ Smoke Detector

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue , St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

D200-74-00 

I56-1195-01R

 

©2001 System Sensor

Three-Year Limited Warranty

System Sensor warrants its enclosed smoke detector base to be free from 
defects in materials and workmanship under normal use and service for a 
period of three years from date of manufacture. System Sensor makes no 
other express warranty for this smoke detector base. No agent, represen-
tative, dealer, or employee of the Company has the authority to increase 
or  alter  the  obligations  or  limitations  of  this  Warranty.  The  Company’s 
obligation of this Warranty shall be limited to the repair or replacement 
of any part of the smoke detector base which is found to be defective in 
materials or workmanship under normal use and service during the three 
year  period  commencing  with  the  date  of  manufacture.  After  phoning 
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return 
Authorization  number,  send  defective  units  postage  prepaid  to:  System 
Sensor,  Repair  Department,  RA  #__________,  3825  Ohio  Avenue,  St. 

Charles, IL 60174. Please include a note describing the malfunction and 
suspected cause of failure. The Company shall not be obligated to repair 
or  replace  units  which  are  found  to  be  defective  because  of  damage, 
unreasonable  use,  modifications,  or  alterations  occurring  after  the  date 
of  manufacture.  In  no  case  shall  the  Company  be  liable  for  any  conse-
quential or incidental damages for breach of this or any other Warranty, 
expressed or implied whatsoever, even if the loss or damage is caused by 
the Company’s negligence or fault. Some states do not allow the exclu-
sion  or  limitation  of  incidental  or  consequential  damages,  so  the  above 
limitation  or  exclusion  may  not  apply  to  you.  This  Warranty  gives  you 
specific legal rights, and you may also have other rights which vary from 
state to state.

Please refer to insert for the Limitations of Fire Alarm Systems