background image

Table D - Craft Connect Functions

Function

Description

INQUIRE

Retrieve and display the unit

*

s configuration status.

DOWNLOAD

Configure the unit using the selected configuration (re-
fer to the title bar). Press <ENTER> to start.

UPLOAD

Retrieve configuration from the unit. Overwrites se-
lected configuration. Press <ENTER> to start.

MONITOR

Monitor operational status. (Fig. 6) Screen shows local
alarm and control point status. (Shown in this screen
only.) It also displays four operational status points, for
use by DPS Technical Support. Press F7 for the Modem
Tuning window.
This function is not fully implemented at this time.

Terminal - PAD Observe data on any port. Select port with function key.

QUIT

Exit this function and return to the Main Menu.

Modem Tuning

If the MUX is equipped with modems on any of the ports, set

the modem levels while in the monitor mode. Press F7 to access
the Modem Tuning Window (Fig. 10). Use the + (plus) and -
(minus) keys to select the port (selected port is displayed in the
first field of the window). With a level meter on the port to be
adjusted, use the keys listed in the window to control the trans-
mit and raise or lower the level, as needed. The receive portion
of the modem has an AGC input, so requires no adjustment.

NOTE: Do not tune above -4dbm or below -34dBm as the

waveforms become distorted at those levels.

Reports

Use this menu item to run configuration reports to the screen,

printer or file. Reports are useful in creating records and refer-
ence files. Such files allow future reference to see how a partic-

ular unit is configured. Several configurations can be reported.
A query box will ask for starting and ending configuration
names (press Tab to see a default box listing of existing config-
urations), report destination and file name (if outputting to file).

Software Parameters

Before a configuration can be downloaded, it is necessary to

set the configuration computer’s com port to match the MUX
craft port parameters. That is done in the Software Parameters
function. See Fig. 11 and Table E.

A sub-menu appears when this function is selected. Select

“Communications” from this sub-menu.Parameters and their
values are given in Table E. Select “Parameters” if you wish to
specify the report directory (Fig. 12).

Table E - Software Parameters Functions

Function

Description

COM

PC Com Port number (1-4).

BAUD

Set only at 9600 Baud.

STOP BITS

Select 1.

DATA BITS

Select 8.

PARITY

Select NONE.

MAX TIMEOUT Time to wait for a response (50-9999 Milliseconds). De-

fault is 3000.

MAX RESEND Number of requests before a timeout will be declared

(0-100). Default is 20.

SEND DELAY

Amount of time before the next request is made. (1-100
seconds). Default is 1.

DIAL TYPE

Not applicable.

QUIT

Exit this function and return to the Main Menu.

Parameters Menu Item

Report Path

Specify the Directory for report files. Normally this is
“Tconfig. See Fig. 12.

4

D-PC-180-10A-XV

March 1997

Fig. 10 - Press F7 while in the Monitor Mode to Access the

Tune Modem Window

Fig. 11 - Configuration Computer Com Port Parameters

must be set before Downloading the MUX

Fig. 9 - Monitor Screen Shows Status of Auxiliary Alarms

and Control Relay

Fig. 12 - Select “Parameters” from the Software Parame-

ters Menu to Define the Directory for Reports

Summary of Contents for ASCII MUX

Page 1: ...ted with each port is a docking module socket that allows the physical interface to the outside world to be configured to match the as sociated communications channel or device This model of the ASCII...

Page 2: ...to the Configuration Section below for more information Configuration The MUX is configured with a program called T ASCMUX T ASCMUX runs under a host program called T Config which can host configurati...

Page 3: ...ch of the eight ports and the MUX common Port in this screen Parameters and their val ues are explained in Table B Table B Field Descriptions for the Edit Configuration Screen Field Description Msg Ti...

Page 4: ...eference to see how a partic ular unit is configured Several configurations can be reported A query box will ask for starting and ending configuration names press Tab to see a default box listing of e...

Page 5: ...RED Receiving data on common port BLINKING GREEN Transmitting Data on common port ER1 RED Error condition CFG RED Needs download GREEN Normal mode A1 A4 RED Alarm point active RLY RED Control relay op...

Page 6: ...23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 CTS PORT 7 TXD PORT 7 N C CTS PORT 8 TXD PORT 8 N C N C N C CTRL 1 CO...

Page 7: ...le H Field Descriptions for the Remote Parame ters Screen Job 30 and Up Field Description Job Phantom port number Jobs 30 to 157 will be available once a device has been defined as 8 Port ASCII MUX Po...

Page 8: ...00 2400 and 9600 Baud All specifications are subject to change without notice Options Model Numbers The ASCII MUX part numbers and options are listed below These options are constantly expanded As a r...

Reviews: