background image

Utilities

Use this menu item to copy or delete configurations and to

perform corrective functions at the direction of DPS technical
support.

A sub-menu appears when this function is selected. See Fig.

13 and Table F.

Table F - Utilities Functions

Function

Description

COPY ASCII

MUX

Copies another configuration into the selected
configuration.

REBUILD KEY

FILES

Repairs damaged index files. Use only at the direction
of DPS technical support.

DELETE ASCII

MUX

Deletes the selected configuration from the database.

TERMINAL

General purpose dumb terminal.

QUIT

Exit this function and return to the Main Menu.

NOTE: The “Selected Configuration” is listed on the Title

Bar at the top of the screen.

Quit

Use this menu item to exit T/ASCMUX.

LED Display Status

Dual-color LED indicators on the front panel give mainte-

nance personnel quick diagnostics of the operational status of
the ASCII MUX. Table G explains the LED functions in detail.

Table G - ASCII MUX LED Display Functions

LED

Condition

Meaning

FA

OFF

Fuse Normal

RED

Fuse Blown

ALM

RED

Craft port is active.

LOD

RED

Download in progress.

LOC

RED

Craft Port active

CM1

BLINKING

RED

Receiving data on common port.

BLINKING

GREEN

Transmitting Data on common port.

ER1

RED

Error condition.

CFG

RED

Needs download.

GREEN

Normal mode.

A1 - A4

RED

Alarm point active.*

RLY

RED

Control relay operated.*

ASCII PORTS

1 - 8

BLINKING

GREEN

Transmitting data on respective port.

BLINKING

RED

Receiving data on respective port.

*Alarm and Control functions are reserved for possible

future use.

ACK Button

The ACK Button performs an LED test. While the ACK but-

ton is held in LED’s will illuminate in their solid color, alternat-
ing from green to red and back.

Hardware Connections

The following illustrations show wiring pinouts for the

MUX.

Craft Port Connector

The Craft Port is a female RS232 DB9 connector used as a

direct link into the MUX. Normally used to configure the
MUX. See Fig. 15.

D-PC-180-10A-XV

5

OG109137

March 1997

Fig. 13 - Select Functions from Utilities Menu

FA

CRAFT

PORT

A1 A2 A3 A4

1

2

6

4

5

6

7

8

RLY

ACK

ALM

CM1

LOD

ER1

LOC

CFG

DPS INC.

ASCII MuX

ALARMS

ASCII PORTS

Fig. 14 - LED Indicators on the Front Panel Show Operational Status of the ASCII MUX

5 4 3 2 1

9 8 7 6

1

2

3

4

5

6

7

8

9

NC

TX

RX

NC

GND

NC

CTS

RTS

NC

Not Connected

Transmit Data

Receive Data

Not Connected

Ground

Not Connected

Clear To Send

Request To Send

Not Connected

PIN # SIGNAL DESCRIPTION

DSR

GND

RTS

CTS

RX

TX

Fig. 15 - Craft Port Pin-Outs

Summary of Contents for ASCII MUX

Page 1: ...ted with each port is a docking module socket that allows the physical interface to the outside world to be configured to match the as sociated communications channel or device This model of the ASCII...

Page 2: ...to the Configuration Section below for more information Configuration The MUX is configured with a program called T ASCMUX T ASCMUX runs under a host program called T Config which can host configurati...

Page 3: ...ch of the eight ports and the MUX common Port in this screen Parameters and their val ues are explained in Table B Table B Field Descriptions for the Edit Configuration Screen Field Description Msg Ti...

Page 4: ...eference to see how a partic ular unit is configured Several configurations can be reported A query box will ask for starting and ending configuration names press Tab to see a default box listing of e...

Page 5: ...RED Receiving data on common port BLINKING GREEN Transmitting Data on common port ER1 RED Error condition CFG RED Needs download GREEN Normal mode A1 A4 RED Alarm point active RLY RED Control relay op...

Page 6: ...23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 CTS PORT 7 TXD PORT 7 N C CTS PORT 8 TXD PORT 8 N C N C N C CTRL 1 CO...

Page 7: ...le H Field Descriptions for the Remote Parame ters Screen Job 30 and Up Field Description Job Phantom port number Jobs 30 to 157 will be available once a device has been defined as 8 Port ASCII MUX Po...

Page 8: ...00 2400 and 9600 Baud All specifications are subject to change without notice Options Model Numbers The ASCII MUX part numbers and options are listed below These options are constantly expanded As a r...

Reviews: