42
For both of your unit's input feeds:
·
Set a
Description
for each of the unit's input feeds, and
·
Click any of the checkboxes 1-8 to indicate what notifications you want the RPS AB6 to send for each
particular input alarm.
Click
Details
to reveal the thresholds for input alarms. All thresholds are listed in Voltage.
·
MjU indicates a Major Under alarm (low voltage). The default value is -40Vdc
·
MnU indicates a Minor Under alarm (low voltage) The default value is -45Vdc
·
MnO indicates a Minor Over alarm (high voltage) The default value is -55Vdc
·
MjO indicates a Major Over alarm (high voltage) The default value is -60Vdc
Once you've configured alarm thresholds and notifications for your power inputs, click
Save
to commit
your changes locally.
Summary of Contents for RPS AB6
Page 6: ...2 Windows Compatibility XP Vista 7 32 64 bit RoHS 5 Approved...
Page 70: ...66...
Page 71: ......
Page 72: ......