8
5. Flip the breaker switch(es) to turn on power.
If the power feeds are connected correctly, you will see LED activity on the front-side of the unit.
Warning
: You must connect both terminals on an input feed to output a full 40 Amps.
Power Output Connection
2.6
The Remote Power Switch's power feeds are wired to 6-pin plug connectors, 3 per connector. For
each output feed, the -48V cable will be on the left and the ground cable (GND) will be on the right.
Power output connectors on the RPS AB6
To connect your power feeds:
1. If connected, remove the front panel fuse for the power input (or set of power inputs) you'll be working
with. (Example: If connecting input feeds A1-A3, ensure that fuses A1, A2, and A3 are disconnected.)
2. If connected, disconnect the 6-pin power connector from the remote power switch before wiring
power outputs.